·Some details are not shown. Please refer to specification sheets for all information.
CTPH
Plug-in Signal Conditioners M-UNIT
CT TRANSMITTER
(true RMS sensing; high speed response; peak hold)
Functions & Features
• Converts an alternating current from a current transformer into a standard process signal
• Dual output: The second output can be switched to ‘peak hold’ mode with the front DIP switch
• Resetting the peak hold output with the front reset control button
• CT Protector provided for open-circuit protection
• True RMS sensing with fast 50-millisecond
response time (0 – 90 %) is possible
• Isolation up to 2000 V AC
Typical Applications
• Monitoring impulsive power line voltage change
MODEL: CTPH–[1][2][3]-[4][5]
ORDERING INFORMATION
• Code number: CTPH-[1][2][3]-[4][5]
Specify a code from below for each [1] through [5].
(e.g. CTPH-5AA-M2/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] INPUT
Current
1
: 0 – 1 A AC
5
: 0 – 5 A AC
[2] OUTPUT 1
Current
A:
4 – 20 mA DC (Load resistance 500 Ω max.)
G
: 0 – 1 mA DC (Load resistance 10 kΩ max.)
Voltage
4
: 0 – 10 V DC (Load resistance 10 kΩ min.)
5
: 0 – 5 V DC (Load resistance 5000 Ω min.)
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
[3] OUTPUT 2 (momentary value or peak hold)
Current
A
: 4 – 20 mA DC (Load resistance 350 Ω max.)
G
: 0 – 1 mA DC (Load resistance 7000 Ω max.)
Voltage
Same range availability as Output 1
[4] POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P
: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
[5] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal:
Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output 1 to output 2 to contact input to power
Input waveform
: Up to 20 % of 3rd harmonic content
Overrange output
: 0 to 120 % at 1 – 5 V
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
Indicator LED
: Red light blinks in 800 millisecond intervals when the power is supplied; blinks in 200 millisecond intervals when the peak hold output is reset.
Function setting
: DIP switch
• Output 2 Function (Momentary value output/Peak hold value output)
• Line Frequency
• Response Time
Reset control
: Used to reset the peak hold output. Momentary value is output immediately after the resetting.
INPUT SPECIFICATIONS
■
CURRENT INPUT
Frequency: 50 or 60 Hz
Input burden: ≤ 0.5 VA
Overload capacity: 500 % of rating for 5 seconds, 120 % continuous
Operational range: 0 – 120 % of rating
■
Contact Input
: Used to reset the peak hold output.
Momentary value is output immediately after the resetting.
Detecting voltage/current
: 15 V DC / approx. 2.5 mA
Detection levels
: ≤ 5 kΩ, ≤ 6 V for ON;
≥ 100 kΩ, ≥ 14 V for OFF
INSTALLATION
Power Consumption
•
AC
:
Approx. 5 VA at 100 V
Approx. 6 VA at 200 V
Approx. 7 VA at 240 V
•
DC
: Approx. 3 W
Operating temperature
: -5 to +60°C (23 to 140°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 240 g (0.53 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.5 %
Temp. coefficient
: ±0.03 %/°C (±0.02 %/°F)
Response time
: ≤ 50/100/200/500 msec. (0 – 90 %)
Peak hold reset time
: 20 msec.
Ripple
: 0.5 %p-p max.
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute
(input to output 1 or output 2 or contact input to power to ground)
500 V AC @ 1 minute (output 1 to output 2 to contact input)
Impulse withstand voltage
: 1.2/50 μsec., ±5 kV (input to output 1 or output 2 or contact input or ground)
EXTERNAL VIEW
DIMENSIONS unit: mm (inch)
TERMINAL ASSIGNMENTS unit: mm (inch)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
MG Co., Ltd.