ES-9695 Rev.3
R8-PA4F
Remote I/O R8 Series
HIGH-SPEED TOTALIZED PULSE INPUT MODULE, 4 points
(NPN input)
Functions & Features
• Space-saving remote I/O module of 4 points input pulse counter
MODEL: R8–PA4FA[1]
ORDERING INFORMATION
• Code number: R8-PA4FA[1]
Specify a code from below for [1].
(e.g. R8-PA4FA/Q)
• Specify the specification for option code /Q
(e.g. /C01)
INPUT
A
: NPN input
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC configurator software (model: R8CFG)
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
Note: When using with Power/Network module (model: R8-NECT1), firmware version Ver1.50 or later is supported.
GENERAL SPECIFICATIONS
Connection
•
Input
: 4-pin e-CON connector
Unit side connector XN2D-1474-S002 (Omron)
Recommended cable side connector XN2A-1470 (Omron)
Applicable wire size: 0.08 - 0.5 mm
2
(AWG28 - 20)
Outer sheath diameter: max. 1.5 dia
(The cable connector is not included in the package.
Refer to the specifications of the product.)
•
Excitation supply, internal bus
:
Connected to internal bus connector
•
Internal power
: Supplied from internal bus connector
Isolation
: Input or exc. supply to internal bus or internal power
Module address
: With rotary switch
Terminating resistor
: Built-in (DIP Switch, default: disable)
Status indicator
: Bi-color (red/green) LED; Refer to the instruction manual.
Input status indicator
: Green LED; Refer to the instruction manual.
INPUT SPECIFICATIONS
Common
: Positive common (NPN) per 4 points
Number of inputs
: 4
I/O status indicator
: LED turns on with closed contact.
∙
NPN input
(internal supply with excitation supply input from network power module)
Rated load voltage
: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / ON current
: ≥ 16 V DC (input terminal to COM) / ≥ 7.2 mA
OFF voltage / OFF current
: ≤ 6 V DC (input terminal to COM) / ≤ 2.5mA
Input current
: 11.2 mA / point (@24 V DC)
Input resistance
: Approx. 2 kΩ
Max. Frequency
: 10 kHz
Min. pulse width requirement
: 20 μsec. for both ON and OFF
Accumulated pulse count
: 0 - 4 294 967 295
Max. accumulable pulse
: 1 - 4,294,967,295 (factory setting: 4,294,967,295)
Overflow reset value
: 0 or 1 (factory setting: 0)
INSTALLATION
Max. current consumption
: 90 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 60 g (2.12 oz)
PERFORMANCE
Data allocation
: 2
Module addresses in use
: 4
Power output (input
connector
)
: Rated current 0.1 A DC per channel (rated current 3 A for internal fuse (slow blow fuse i
2
t (A
2
sec.) max. 0.31); Total: 0.4 A DC
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(input or exc. supply to internal bus or internal power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
OPERATING MODE SETTING
(*) Factory setting
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM