ES-6130 Rev.5
R5-RSA
Remote I/O R5 Series
RTD INPUT MODULE
(high resolution)
MODEL: R5-RSA[1][2][3]
ORDERING INFORMATION
• Code number: R5-RSA[1][2][3]
Specify a code from below for each of [1] through [3].
(e.g. R5-RSA2W/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] NO. OF CHANNELS
1
: 1 channel
2
: 2 channels
[2] COMMUNICATION MODE
S
: Single
W
: Dual
[3] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R5-BS)
Input
: Euro type connector terminal
(Applicable wire size: 0.2 – 2.5 mm
2
(AWG24 - 12),
stripped length 7 mm)
Internal power
: Via the base (model: R5-BS)
Isolation
: Input 1 to input 2 to internal bus or internal power
Sensor type
: Selectable with the side DIP SW
Temperature unit:
°C or °F selectable with the side DIP SW
Burnout detection:
Upscale or downscale selectable with the side DIP SW
Linearization
: Standard
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
INPUT SPECIFICATIONS
Maximum leadwire resistance
: 10 Ω per wire
Sensing current
: ≤ 1 mA
(Factory setting is Pt 100 (JIS '97, IEC))
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R5-BS)
Weight
: 100 g (0.22 lb)
PERFORMANCE
Conversion accuracy
: ±0.1°C (±0.2°F)
Data range
°C
: Engineering unit value × 100 (integer)
°F
: Engineering unit value × 10 (integer)
Data allocation
: 1 (2 for 2-channel type)
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 0.2 sec. (0 – 90 %)
Burnout response time:
≤ 2 sec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input 1 to input 2 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
EXTERNAL VIEW
INPUT DATA DESCRIPTIONS
■ ANALOG DATA (TEMPERATURE DATA)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM