ES-8964 Rev.12

R3Y-DC16

Remote I/O R3 Series

DISCRETE OUTPUT MODULE

(relay contact output, 16 points, connector type)

MODEL: R3Y–DC16[1][2]

ORDERING INFORMATION

• Code number: R3Y-DC16[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R3Y-DC16W/CE/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

NO. OF CHANNELS

16: 16

[1] COMMUNICATION MODE

S: Single
W: Dual

[2] OPTIONS (multiple selections)

Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS

Connection
  Internal bus
: Via the Installation Base (model: R3-BSx)
  Output: 40-pin connector (OTAX N365P040AU
  (Fujitsu FCN-365P040-AU...discontinued))
  Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Output to internal bus or internal power
Output hold setting: Setting for communication error with side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED turns on in normal operating conditions.
Output status indicator: Red LED; turns on with the output ON.

OUTPUT SPECIFICATIONS

Output: Relay contact, 16 points
Common: All 16 points (8 terminals)
Common current: Max. 4A (total of 8 terminals)
(Max. 1 A for one terminal)
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
(Less than 50 V AC to conform with EU Directive)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
Mechanical life: 2 × 107 cycles (300 cycles/min.)
When driving an inductive load, external contact protection and noise quenching recommended.

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE

Data allocation: 1
Current consumption: 180 mA
Response time: ≤ 0.1 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

FUNCTIONS

OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from the preferred bus A.
When an error is detected, the output is switched to the data from the bus B.
Output Hold
If both are in error, the module holds the signal and stands by until one of the communications recovers.
Output OFF
If both are in error, the module outputs OFF signals and stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is established and normal data is received.

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

OUTPUT CONNECTOR (40-pin)