ES-8432 Rev.12
R3-RR8
Remote I/O R3 Series
REMOTE CONTROL RELAY CONTROL MODULE
(Do 8 points)
Functions & Features
• Controls remote control relays for lighting control with Fieldbus
• Applicable to the remote control relays already installed
• Monitors status of remote control relays with feedback inputs from signal lines
Typical Applications
• Monitors and controls of lighting in buildings
MODEL: R3-RR8[1][2]
ORDERING INFORMATION
• Code number: R3-RR8[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-RR8W/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
8
: 8
[1] COMMUNICATION MODE
S
: Single
W
: Dual
[2] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• Interface Module (model: R3-NC1, NC3, NE1, NM1, NM3, NM4, NDx, NF2, NFL1)
Firmware version V2.00 or higher.
R3-NF2 is available with firmware version V0.04 or higher.,
RECOMMENDED PRODUCTS (OPERATION CHECKED)
Remote control relay:
BR-12D, BR-22D (Mitsubishi Electric)
WR6165 (Panasonic)
Remote control transformer:
BRT-10B, BRT-20B (Mitsubishi Electric)
WR2301 (Panasonic)
Remote control switch
WR8501 (Panasonic)
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R3-BSx)
Output
: M3 separable screw terminal (torque 0.5 N·m)
Internal power
: Via the Installation Base (model: R3-BSx)
Screw terminal
: Nickel-plated steel
Isolation
: Output to internal bus or internal power
Input Data Length
: 8 bit, 16 bit selectable with DIP switch
Output data length
: 8 bit, 16 bit selectable with DIP switch
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Green LED;
OFF in abnormality; ON in normal operating conditions.
Input output status indicator
: Red LED;
1 to 8
: Output bit status, turns on with bit set ON.
9 to 16
: Feedback input status, turns on with the input ON.
OUTPUT SPECIFICATIONS
Number of output
: 8 points
Common
: All 8 points (12 terminal)
Rated load voltage
: 24 V AC ±10 % (supplied by the remote control transformer)
Load voltage frequency
: 50 / 60 Hz
Maximum outputs provided at once
: No limit
Output ON duration
: 100 msec.
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Data allocation
: 1
Current consumption
: 40 mA
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(output to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
INPUT OUTPUT DATA BIT & DATA ALLOCATION
DATA ASSIGNMENT
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]