ES-8358 Rev.13
R3-PS3
Remote I/O R3 Series
POWER SUPPLY MODULE
(double slot, continuous output current 2.0 A)
MODEL: R3-PS3-[1][2]
ORDERING INFORMATION
• Code number: R3-PS3-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-PS3-K3/CE/B/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] POWER INPUT
AC Power
K
: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
(CE not available)
K3
: 100 – 120V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
(Only /CE available)
L
: 170 – 264 V AC
(Operational voltage range 170 – 264 V, 47 – 66 Hz)
(CE Not available)
L3
: 200 – 240 V AC
(Operational voltage range 170 – 264 V, 47 – 66 Hz)
(Only /CE available)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P
: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
(CE not available)
[2] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Housing (refer to the external dimensions)
blank
: Standard type
/B
: Type B
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Connection
Internal power output
: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output
: M3 separable screw terminal (torque 0.5 N·m)
Screw terminal
: Nickel-plated steel
Isolation
: Internal power to power input to RUN contact output to FG
Power indicator LED
: Green LED turns on when the power is supplied.
■
RUN CONTACT OUTPUT
RUN contact
: Turns on (closed) while the power is supplied.
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage:
250 V AC or 30 V DC
Maximum switching power:
250 VA or 150 W
Minimum load:
1 V DC @ 1 mA
Mechanical life:
2 × 10
7
cycles (rate 300 cycles/min.) When driving an inductive load, external contact protection and noise quenching recommended.
INSTALLATION
Power consumption
(Output current: 2.0 A @ 20 V DC)
•
AC
: Approx. 100 VA
•
DC
: Approx. 50 W or 2.0 A at 24 V
Output current
: 2.0 A continuous at 20 V DC;
2.2 A for 10 minutes
(For dual power supply, the specification of output current is same. Total current continuously consumed at the network modules, I/O modules and interface I/O modules must be within 2.0 A.)
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 450 g (0.99 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute
(internal power to power input to RUN contact output to FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Measurement Category II (RUN contact output)
Installation Category II (power input)
Pollution Degree 2
Internal power to power input: Reinforced insulation
(300 V)
Internal power to RUN contact output: Basic insulation
(300 V)
RoHS Directive
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM