ES-8457 Rev.12

R3-PA8

Remote I/O R3 Series

TOTALIZED PULSE INPUT MODULE

(Pi 8 points, 32 Bits)

MODEL: R3-PA8[1][2]

ORDERING INFORMATION

• Code number: R3-PA8[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R3-PA8W/A/CE/PRS/Q)
• Specify the specification for option code /Q
  (e.g. /C01/SET)

NO. OF CHANNELS

8: 8

[1] COMMUNICATION MODE

S: Single
W: Dual

[2] OPTIONS (multiple selections)

Excitation
Blank: Internal (negative common)
/A: External (24 V DC, negative common)
Standards & Approvals
blank: Without CE
/CE: CE marking
EX-FACTORY SETTING
blank: Enable count reset by host PC/PLC 
/PRS: Enable count preset by host PC/PLC
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
 (No. ESU-8457)

RELATED PRODUCTS

 • Interface module (model: R3-NC1, R3-NC3, R3-NE1,
R3-NMx, R3-NDx, R3-NFL1, R3-NP1, R3-NFx, R3-NML3. 
R3-NF2: Firmware version V0.05 or later)
Note:
 • Count reset by host PC/PLC:
Available with this unit and the above mentioned interface modules of firmware version V2.00 or later, except R3-NFx (R3-NM3: Firmware version V1.00 or later). Notice that Count reset by host PC/PLC via R3-NFx or interface module of previous versions of firmware is unable.
 • Count preset by host PC/PLC:
It is only available in combination with this unit displayed 'SW3-4 RESET/PRESET' on the right side panel and the interface module R3-NMx or R3-NE1 of firmware version V2.00 or later. Count preset is not available for other combination (R3-NM3: Firmware version V1.00 or later).
Notice that this function is not available in the same time as count preset by host PC/PLC.
 • In the FL-net Configuration Builder software (model: R3-NFLBLD), the number of channel for this module is displayed as 16 because data has 8 channels x 2 words.

GENERAL SPECIFICATIONS

Connection
 Internal bus: Via the Installation Base (model: R3-BSx)
 Input: M3 separable screw terminal (torque 0.5 N·m)
 Internal power: Via the Installation Base
 (model: R3-BSx)
Screw terminal: Nickel-plated steel
Isolation: Input to internal bus or internal power
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with excitation abnormality;
Green in normal operating conditions.
Input status indicator: Red LED;
  1 to 8: Turns on with the input ON.
  9 to 15: Unused 
  16: Turns on with the reset input ON.
Count reset: Via DIP switch on the side or one pulse to reset input
Count setting from host PC/PLC: Count reset/count preset is changeable via DIP switch on the side.

INPUT SPECIFICATIONS

Number of input: 9 (8 points + Count reset)
Input resistance: 6 kΩ
Common: Negative commons, all points; 2 terminals
Maximum frequency: 100 Hz
(ON/OFF time ≥ 5 msec.)
This unit is designed to be able to accept a frequency up to 100 Hz, however,‘chattering’ contact must be avoided for accurate measuring of such high frequency. Use relays that do not cause any chattering.
Totalized pulse range: 0 - 9999999
Count at overflow: Reset and restart at ‘0.’
Max. pulse range selectable from 10000 to 2147483647 using the R3CON PC Configurator Software. ‘0’ or ‘1’ from which restart counting at overflow is pre-settable. Refer to the R3CON Users Manual for detailed information.
R3-PA8x (internal excitation)
Sensing voltage
: 13 V DC (max. 24 V with no load)
ON voltage: ≥ 9 V (≤ 1.5 kΩ)
OFF voltage: ≤ 4.5 V (≥ 18 kΩ)
R3-PA8x/A (external excitation)
Sensing voltage
: 24 V DC
ON voltage: ≥ 9 V (≤ 12 kΩ)
OFF voltage: ≤ 4.5 V (≥ 36 kΩ)

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE

Data allocation: 16
Current consumption: 70 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute
(input to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

COUNT RESET

There are three different ways to reset count value.
■ COUNT RESET WITH DIP SW
1) Remove Network Module or its cables and interrupt communication with other devices.
2) Turn ON the Count Reset SW (DIP SW3-1) on R3-PA8 module.
3) Return the module to the base and turn the power supply on.
4) ERR LED turns on and the module starts resetting its counter.  When the resetting is complete, the LED turns to green.  DO NOT remove the power while the red LED is on.
5) After confirming that ERR LED is green, turn the power supply off.
6) Turn OFF the Count Reset SW (DIP SW3-1).
7) Return the Network module onto the base and turn the power supply on.
Note: Count Reset SW must be turned OFF after this procedure because the module does not start counting with ON state.  Even when the count overflow set value is 1, the counter is reset to 0.
■ COUNT RESET WITH RESET SIGNAL
With the Count Reset Input SW (DIP SW3-3) turned ON, the count reset signal value becomes effective.
  SW3-3 = OFF: invalid
  SW3-3 = ON: valid
One pulse supplied at the Count reset input terminal will be recognized as a reset signal.
1) ERR LED turns on (red color) when the reset signal is received.
2) In 1 second, the module starts resetting its counter.  When the resetting is complete, the LED turns to green.
3) After 1 second, ERR LED turns back to the state before the reset signal has been received.
Note: Reset signals received while the module is processing (1) through (3) are ignored.  Even when the count overflow set value is 1, the counter is reset to 0.
■ COUNT RESET FROM HOST PC/PLC
Refer to “COUNTER SETTING FROM HOST PC/PLC” section hereafter.

EXTERNAL VIEW

COUNTER SETTING FROM HOST PC/PLC

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM