ES-9003 Rev.4

R30RS4

Remote I/O R30 Series

RTD INPUT MODULE

(4 points, isolated)
Functions & Features
• 4 channels for RTD input remote I/O module
• Isolation between input channels
• Input range of each channel is individually adjustable with PC configurator

MODEL: R30RS4S[1]

ORDERING INFORMATION

• Code number: R30RS4S[1]
Specify a code from below for [1].
  (e.g. R30RS4S/Q)
• Specify the specification for option code /Q
  (e.g. /C01/SET)

NO. OF CHANNELS

4: 4

COMMUNICATION MODE

S: Single

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
 (No. ESU-9003)

CAUTION

UNUSED INPUT CHANNELS
Set unused channels to "CH disabled" with PC Configurator software (model: R30CFG).  Otherwise, unused channels left open are to be burnout status, setting a data error at the PLC or other host devices.

RELATED PRODUCTS

• PC configurator software (model: R30CFG)
Downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)

GENERAL SPECIFICATIONS

Connection
 Internal bus
: Via the Installation Base (model: R30BS)
 Input: M3 separable screw terminal (torque 0.5 N·m)
 Internal power: Via the Installation Base (model: R30BS)
Solderless terminal: Refer to the drawing at the end of the section.
   Recommended manufacturer: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd. 
  (Solderless terminals with insulation sleeve do not fit.)
  Applicable wire size: 0.25 to 0.75 mm2
Screw terminal: Nickel-plated steel
Isolation: Input 1 to input 2 to input 3 to input 4 to internal bus or internal power
Input range: Selectable with PC configuration software (model: R30CFG)
Conversion rate: Selectable with PC configuration software (model: R30CFG)
Burnout: Selectable among upscale, downscale or no burnout with PC configurator software (model: R30CFG)
Linearization: Standard
Status indicator LED: RUN, ERR
(refer to the instruction manual)
■Recommended solderless terminal size - M3 (unit: mm)

INPUT SPECIFICATIONS

Module type: Analog input, 4 points
RTD: Pt 100 (JIS ’97, IEC), Pt 100 (JIS ’89), JPt 100 (JIS ’89), Pt 50Ω (JIS ’81),  Ni 100, Cu 10, Cu 50
Sensing current
: Max. 1 mA
Allowable leadwire resistance: Max. 100 Ω per wire

INSTALLATION

Current consumption: 50 mA max.
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R30BS)
Weight: 160 g (0.35 lb)

PERFORMANCE

Conversion accuracy: ±1°C (±1.8°F) except ±3°C (±5.4°F) for Cu 10 @ 25°C
Conversion rate: 250 msec. or 500 msec. selectable
Converted data range
  °C, K: Engineering unit value × 10 (integer) (Default setting)
  °F: Engineering unit value (integer)
* Scaling of converted data is configurable with the configurator software (model: R30CFG). Refer to the software manual for details. 
Data allocation: 4
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Input delay time: 50 msec.
Response time: Conversion rate × 2 + 50 msec. (0 – 90 %)
Burnout response time: ≤ 1 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input 2 to input 3 to input 4 to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

CONFIGURATOR SOFTWARE SETTING

The following parameters can be set with using PC Configurator Software (model: R30CFG)
Refer to the users manual for the R30CFG for detailed operation of the software program.

EXTERNAL VIEW

TERMINAL ASSIGNMENTS

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM