ES-9022 Rev.3

R30PA2

Remote I/O R30 Series

TOTALIZED PULSE INPUT MODULE

(Pi 2 points, 32 Bits)
Functions & Features
• Space-saving remote I/O module of 2 points input pulse counter
• 32-bit binary data

MODEL: R30PA2S[1]

ORDERING INFORMATION

• Code number: R30PA2S[1]
Specify a code from below for [1].
  (e.g. R30PA2S/Q)
• Specify the specification for option code /Q
  (e.g. /C01/SET)

NO. OF CHANNELS

2: 2

COMMUNICATION MODE

S: Single

[1] OPTIONS

Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
 (No. ESU-9022)

RELATED PRODUCTS

• Interface module
  Model: R30NECT1 (firmware version V1.04.10 or higher)
  Model: R30NCIE1 (firmware version V1.01.13 or higher)
• Paperless recorder
  Model: TR30 (firmware version V1.05 or higher)
• PC configurator software (model: R30CFG)
Downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)

GENERAL SPECIFICATIONS

Connection
 Internal bus
: Via the Installation Base (model: R30BS)
 Input: M3 separable screw terminal (torque 0.5 N·m)
 Internal power: Via the Installation Base (model: R30BS)
Solderless terminal: Refer to the drawing at the end of the section.
   Recommended manufacturer: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd. 
  (Solderless terminals with insulation sleeve do not fit.)
  Applicable wire size: 0.25 to 0.75 mm2
Screw terminal: Nickel-plated steel
Isolation: Input or reset input or external power to internal bus or internal power
Status indicator LEDs: RUN, ERR
Input status indicator LEDs: Green LED; turns on with input ON
(Refer to the instruction manual.)
Count reset: by inputting one pulse to the reset input terminal, or from host PC/PLC
Count preset: settable from host PC/PLC, or with PC configurator software
■Recommended solderless terminal size - M3 (unit: mm)

INPUT SPECIFICATIONS

Module type: Pulse input, 2 points
Common: Positive or negative common (NPN/PNP), common per 2 points
Contact Input / Reset Input
Open collector input (NPN, PNP)
 Rated input voltage: 24 V DC ±10 %; ripple 5 %p-p max.
 ON voltage/current: ≥ 16 V DC (input to common) / 
 ≥ 3.7 mA
 OFF voltage/current: ≤ 5 V DC (input to common) / ≤ 1 mA
Voltage Pulse Input
 ON voltage/current: ≥ 16 V DC (input to common) / 
 ≥ 3.7 mA
 OFF voltage/current: ≤ 5 V DC (input to common) / ≤ 1 mA
Input current: ≤ 5.5 mA per point at 24 V DC
Input resistance: Approx. 4.4 kΩ
ON delay: ≤ 2.0 msec.
OFF delay: ≤ 2.0 msec.
Max input frequency: 100 Hz
Minimum pulse width time requirement: 5 msec. (for both ON and OFF)
Totalized pulse range: 0 to 4,294,967,295 (0 only when the counter is reset)
Max pulse range: 1 to 4,294,967,295
(factory setting: 4,294,967,295)
Count at overflow: 0 or 1 (factory setting: 0)

INSTALLATION

Current consumption: 30 mA max.
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R30BS)
Weight: 150 g (0.33 lb)

PERFORMANCE

Data allocation: 4
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input or reset input or external power to internal bus or internal power)
1500 V AC @ 1 minute (power to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

CONFIGURATOR SOFTWARE SETTING

The following parameters can be set with using PC Configurator Software (model: R30CFG)
Refer to the users manual for the R30CFG for detailed operation of the software program.

EXTERNAL VIEW

TERMINAL ASSIGNMENTS

DATA ALLOCATION

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]