ES-9186 Rev.1

NF-LWA

NOISE FILTER FOR LonWorks

(FTT-10A)
Functions & Features
• Compatible to FTT-10A network
• Satisfies the specifications of insulation choke for FTT-10A network recommended by Echelon 

MODEL: NF–LWA

ORDERING INFORMATION

• Code number: NF-LWA-1

SHIELD TERMINAL

1: With

APPLICABLE NETWORK

LonWorks FTT-10A network
This unit is not applicable to LonWorks Link Power network.

GENERAL SPECIFICATIONS

Connection:
 Network: Euro type connector terminal
 (Applicable wire size: 0.2 to 2.5 mm2)
 Ground: M3 screw terminals (torque: 0.6 N·m)
Screw terminal: Nickel-plated brass
Housing material: Flame-resistant resin (black)

INSTALLATION

Operating temperature: -25 to +70°C (-13 to +158°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Mounting: DIN Rail (TH35-7.5, 1-mm-thick)
When this unit is earthed via a DIN rail, use a steel or copper rail. Oxide film on the surface of an aluminium rail may lower the electric conductivity between this module and the ground.
Weight: 80 g (2.8 oz)

PERFORMANCE in percentage of span

Dielectric strength: 500 V AC @ 1 minute (NetA to NetB to SHLD or G)
Series resistance: ≤ 1.5 Ω
Inductance value: ≥ 1.8 mH @ 10 kHz 
Capacitance: 40 pF @ 10 kHz

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM