ES-1731 Rev.12
MXAP
Plug-in Signal Conditioners MX-UNIT
DC/FREQUENCY CONVERTER
(front configurable)
Functions & Features
• Provides a pulse rate output in proportion to DC input signal
• Field-programmable output frequency and
pulse width
• Easy programming via front UP-DOWN keys
with a help of 4-digit and 2-digit displays
• Low-end cutout
• Pulse totalizing function (manual/auto reset)
• Loop test output
• Isolation up to 2000 V AC
• High-density mounting
Typical Applications
• Totalizing applications in combination with a counter
MODEL: MXAP–[1][2]–[3][4]
ORDERING INFORMATION
• Code number: MXAP-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. MXAP-S1F-M2/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01/SET)
[1] INPUT
Current
Z1
: Range 0 – 50 mA DC (Input resistance 100 Ω)
Voltage
S1
: Range -1 – + 1 V DC (Input resistance 100 kΩ min.)
S2
: Range -10 – +10 V DC (Input resistance 1 MΩ min.)
S3
: Range -30 – +30 V DC (Input resistance 1 MΩ min.)
[2] OUTPUT
A
: Open collector (10 kHz)
F
: Voltage pulse (10 kHz)
J
: RS-422 line driver pulse (10 kHz)
R
: AC/DC switch (10 Hz)
( ) = Max. frequency conforming with the described accuracy.
[3] POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R3:
12 – 24 V DC
(Operational voltage range 10.8 - 26.4 V, ripple 10 %p-p max.)
P
: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
[4] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-1731)
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Programming
: Via front keys
• Input range
• Low-end cutout
• Output frequency range
• Pulse width
• Output logic
etc...
(Refer to the instruction manual for details)
Low-end cutout
: Programmable within 0.3 – 100 %; deadband 0.1 %; Cancelled in the loop test output mode or when 0 % output frequency is set to a frequency other than 0 Hz.
■
DISPLAY
LED
: 8 mm (.31”) 7 segment, red
Number of display digits
: 4 digits for DATA display; 2 digits for ITEM display
Scaling
: -9999 to 9999
PV indication
: Input signal in engineering unit
Totalized pulse count
: 0 – 99999999; Blinks at overflow.
Overrange indication
: LEDs blinking
Power saving mode
: Displays turn off if the keys are untouched for a preset time period
Status LEDs
: Red; the PL1 turns on with negative polarity, the PL2 with programming error and the PL3 with low-end cutout.
Output LED
: Red; the PL4 blinks in synchronization with the output pulse; remains on at 30 Hz or higher frequencies.
INPUT SPECIFICATIONS
■
DC Current
: 0 – 50 mA DC; shunt resistor attached to input terminals (0.5 W)
Operational range
: 0 – 70 mA DC (with 100 Ω/0.5 W)
Default setting:
4.0 – 20.0 mA DC
■
DC Voltage
•Code S1
: -1.00 – +1.00 V DC
Operational range
: -1.15 – +1.15 V DC
Minimum increment
: 10 mV
•Code S2
: -10.0 – +10.0 V DC
Operational range
: -11.5 – +11.5 V DC
Minimum increment
: 100 mV
•Code S3
: -30.0 – +30.0 V DC
Operational range
: -34.5 – +34.5 V DC
Minimum increment
: 100 mV
Note: 100 % input must be larger than 0 %.
Default setting:
Code S1
: -1.00 – +1.00 V DC
Code S2
: -10.0 – +10.0 V DC
Code S3
: -30.0 – +30.0 V DC
OUTPUT SPECIFICATIONS
100 % output frequency must be higher than 0 %.
Note: Minimum increments is 1/1000 of each frequency range.
•
Open Collector
: 50 V DC @ 50 mA (resistive load)
Frequency range
: 0 – 10 pulses/hour through 10 kHz
Saturation voltage
: 0.6 V DC
■
Voltage Pulse
Frequency range
: 0 – 10 pulses/hour through 10 kHz
Lo level
: ≤ 0.5 V
Hi level
: 5 – 24 V ±10 %
(selectable in 1 V increments)
Load resistance
: 5 kΩ minimum
■
AC/DC Switch
: 120 V AC/DC @ 200 mA (resistive load)
Frequency range
: 0 – 10 pulses/hour through 10 Hz
On resistance
: 3 Ω
Rise time
: 5 msec.
Sink time
: 3 msec.
■
RS-422 Line Driver Pulse
Frequency range
: 0 – 10 pulses/hour through 10 kHz
Conforms to EIA/TIA-422-B
OUTPUT PULSE WIDTH
■
DUTY RATIO 50 %
(approx.)
The duty ratio remains at 50 % (approx.) even when the output frequency changes.
■
ONE-SHOT OUTPUT
The output pulse width varies by 10 % of the preset value.
Selectable from 1 msec. up to 10 sec. (50 msec. – 10 sec. for AC/DC switch).
For 10 kHz and a part of 1 kHz ranges, the one-shot output is not selectable. Choose 50 % duty ratio for such cases.
If the preset value is wider than the cycle at 115 % output, this unit does not function properly related ITEM number blinks.)
[Example] 0 % output frequency = 50 Hz
100 % output frequency = 100 Hz
115 % output cycle = 9.3 msec.
The output pulse greater than 9.3 msec. is not appropriate.
INSTALLATION
Power consumption
•
AC
:
approx. 3.5 VA at 100 V
approx. 5 VA at 200 V
approx. 7 VA at 264 V
•
DC
: Approx. 3.3 W (130 mA at 24 V)
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 450 g (0.99 lb)
PERFORMANCE
Accuracy
: Input + output
Input
: ±0.05 %
(When span is set to not less than 20 % of settable range)
Output
: ±0.3 % at 10 kHz range
±0.05 % at 1 kHz or lower range
(When span is set to not less than 20 % of settable range)
Display accuracy
: Input accuracy ±1 digit
(with 0.0 – 100.0 scaling)
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: 0.3 sec. + (one pulse cycle at 100 % output)
Time required from a step input (0 – 100 %) to the first pulse output.
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Input to output to power: Basic insulation (300 V)
RoHS Directive
EXTERNAL VIEW
Refer to the instruction manual for detailed procedures.
OUTPUT LOGIC
RECALLING PAST TOTALIZED COUNT
EXTERNAL DIMENSIONS unit: mm [inch]
TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM