ES-8132 Rev.12

MDP-JS

Lightning Surge Protectors for
Electronics Equipment M-RESTER

LIGHTNING SURGE PROTECTOR FOR
SELF-SYNCH USE

Functions & Features
• Designed specifically for self-synchronizing motor circuit
• Protects self-synch transmitter and converter from damage caused by surges on the wiring
• Absorbs surges only without affecting instrumentation signal
• No interruption of signal by unplugging the protector element

MODEL: MDP–JS[1]

ORDERING INFORMATION

• Code number: MDP-JS[1]
Specify a code from below for [1].
  (e.g. MDP-JS/A33/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS (multiple selections)

DIN Rail Mounting Adapter
blank: Without
/A33: With adapter (model A-33)
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M4 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)

INSTALLATION

Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 100 g (0.22 lb), standard; 125 g (0.28 lb), with DIN rail mounting adapter

PERFORMANCE

Max. continuous operating voltage (Uc): 
 A to B to C: ±170 V   
 Line to earth: ±290 V
Voltage protection level (Up):
• @ 1 kV (100 A)
 1 to 2 to 3: ±350 V  
 Line to earth:  ±650 V
• @ 2 kV (1 kA) 
 1 to 2 to 3: ±450 V  
 Line to earth: ±800 V
Response time: ≤ 0.1 μsec.
Leakage current:
 A to B to C: ≤ 50 μA @ ±170 V DC
 Line to earth: ≤ 50 μA @ ±290 V DC
Max. discharge current (Imax): 5000 A (8 / 20 μs)
Nominal current (IN): 500 mA
Internal series resistance: Approx. 2 Ω (per wire)
Rated line voltage: 90 V AC
Capacitance @ 1 MHz:
 Line to line:  ≤ 1.5 nF
 Line to earth: ≤ 50 pF
Surge protection: IEC 61643-21 Categories C1, C2, D1

CONNECTION EXAMPLES

GROUNDING

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM