ES-8205 Rev.2

MDA-TL

Lightning Surge Protectors for
Electronics Equipment M-RESTER

LIGHTNING SURGE PROTECTOR FOR
ANALOG TELECOM LINE USE

(life monitor)
Functions & Features
•Designed specifically to protect telecommunication equipment from lightning surges entering through telecommunication line network
•Absorbing surges only without affecting instrumentation signal
•Life monitor function helps you to decide when you should replace the M-RESTER; reduces maintenance and prevents downtime
•LED display and alarm contact output indicate the degradation and life span of the surge protection circuits

MODEL: MDA–TL–[1]

ORDERING INFORMATION

• Code number: MDA-TL-[1]
Specify a code from below for [1].
  (e.g. MDA-TL-M)

[1] POWER INPUT

AC Power
M: 85 – 264 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R2: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
  Telecom line: Modular jack or M3.5 screw terminals
  (torque 0.8 N·m);
  Line screw terminal connection must be handled by
  qualified personnel.
  Ground: M3.5 screw terminals (torque 0.8 N·m)
Modular jack cord: 6-pole, 2-core
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Alarm indicators
  Power
: The green LED turns on while the power is supplied.
  Alarm: Tricolor LED (green/amber/red)
  •Remains off when the power supply is first turned on.
  •Green: The unit has received one or more surges.
  •Amber: Replacement is recommended.
  •Red: The life span has ended.
  Life time judged: When the number of discharges
  of the discharge element reaches the expected life span.
Alarm contact: The N.C. contact is on when the life span of the discharge elements has ended and/or when the power supply is removed.
  Rating: 125 V AC @ 0.5 A (cos ø = 1)
  30 V DC @ 1 A (resistive load)
  Maximum switching voltage: 125 V AC or 110 V DC
  Maximum switching power: 62.5 VA or 30 W
  Minimum load: 5 V DC @ 1 mA

INSTALLATION

Power consumption
AC: Approx. 2 VA at 100 V
 Approx. 3 VA at 200 V
 Approx. 4 VA at 240 V
DC: Approx. 1.5 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail; Standard Rack Mounting Frame BX-16H available
Weight: 150 g (0.33 lb)

PERFORMANCE

Discharge voltage (peak voltage)
  Line to line: ±190 V min.
  Line to ground: ±180 V min.
Maximum surge voltage
  Line to line: ±500 V max.
  Line to ground: ±900 V max.
(The maximum voltage that could pass through M-RESTER. Protected equipment must be able to withstand this voltage for very short time period.)
Response time: ≤ 0.01 μsec.
Leakage current:
  Line to line: ≤ 100 μA @ ±160 V DC
  Line to ground: ≤ 100 μA @ ±160 V DC
Discharge current capacity
  Modular jack connection
: 500 A (8 / 20 μsec.)
  Screw terminal connection: 10000 A (8 / 20 μsec.)
Maximum load current: 200 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
(surge protector circuit to alarm output to power)
Dielectric strength: 2000 V AC @ 1 minute (surge protector circuit to power to alarm output to ground)
Internal series resistance: Approx. 4 Ω including return
Maximum line voltage: ±160 V DC
Frequency band: Approx. 100 kHz/-3 dB at 600 Ω terminating resistance

EXTERNAL VIEW

GROUNDING

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM