ES-5403 Rev.2

M80DY

Super-mini Signal Conditioners M80 Series

CURRENT LOOP SUPPLY

Functions & Features
• Powering a 4 – 20 mA DC current loop
• Space-saving, easy to-maintain, multi-channel installation base
• Isolates between analog output channels of a PLC

MODEL: M80DY-A6-R

ORDERING INFORMATION

• Code number: M80DY-A6-R

INPUT

Current
A: 4 – 20 mA DC (Input resistance approx. 249 Ω)

OUTPUT

Voltage
6: 1 – 5 V DC (Load resistance 10 kΩ min.)

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

RELATED PRODUCTS

• Installation Base (model: M80BS-x1x-R)
This unit must be mounted on a dedicated base.

GENERAL SPECIFICATIONS

Construction: Plug-in
Housing material: Flame-resistant resin (gray)
Power supply: Via the Installation Base terminals
(model: M80BS-x1x-R)
Isolation: Input to output to power
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)

SUPPLY OUTPUT

Output voltage: 22 – 32 V DC with no load
Current rating: ≤ 22 mA DC
Shortcircuit Protection
Current limited
: 30 mA max.
Protected time duration: ≦ 1 min.

INPUT SPECIFICATIONS

DC Current: Input resistor incorporated

INSTALLATION

Current consumption: Approx. 80 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 5 to 95 %RH (non-condensing)
Mounting: Multi-channnel Installation Base (model: M80BS-x1x-R)
Weight: 20 g (0.71 oz)

PERFORMANCE in percentage of span

Accuracy: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 15 msec. (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1000 V AC @1 minute  (input to output to power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM