ES-5398 Rev.5

M80BS-8

Super-mini Signal Conditioners M80 Series

INSTALLATION BASE (8 positions)

Functions & Features
• Holds up to 8 modules of M80 series signal conditioners
• Distributes power from a common power source; individual power wiring not required
• Requires only a limited wiring work within an instrumentation panel

MODEL: M80BS-8[1][2]-R

ORDERING INFORMATION

• Code number: M80BS-8[1][2]-R
Specify codes from below for each of [1] and [2].
  (e.g. M80BS-811-R)

[1] I/O TYPE

1: Input (M80YV, etc.)
2: Output (M80YS, etc.)

[2] CONNECTION

1: CN1 3M Company 3428-6002 LCPL
    CN2 Without
2: CN1 3M Company 3428-6002 LCPL
    CN2 3M Company 3428-6002 LCPL

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

RELATED PRODUCTS

• Connector terminal block (model: CNT)
• Special cable (model: MCN201)

GENERAL SPECIFICATIONS

Capacity: 8 positions
Connection
Power input: M3 screw terminals (torque 0.6 N·m)
I/O teminal: M3 screw terminals (torque 0.6 N·m)
I/O connector: 3M Company 3428-6002 LCPL
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Input to output to power to FG
Power indicator LED: Turns On when power is supplied

INSTALLATION

Current consumption: ≤ 0.6 A
Arrange in order that the total current consumed by the modules is within 0.5 A.
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 5 to 95 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 250 g (0.55 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1000 V AC @1 minute  (input to output to power or FG)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

CONNECTION DIAGRAM

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]