Functions & Features
• Converts DC input from a sensor into a standard process signal
• Output range and response time selectable with DIP SW
• Power connector for interconnecting modules and collectively supplying power
• Spring clamp terminal connection for easy wiring
• 6-mm wide ultra-slim design
• Low profile allows mounting in a 120-mm deep panel
• High-density mounting
• Power indicator LED

MODEL: M60SVS-R[1]

ORDERING INFORMATION

• Code number: M60SVS-R[1]
Specify a code from below for [1].
  (e.g. M60SVS-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)
• Default at shipment
  Input range: 4 – 20 mA DC
  Output range: 4 – 20 mA DC
  Response time: Standard response

INPUT – Field-selectable

Current
4 – 20 mA DC (Input resistance 50 Ω)
0 – 20 mA DC (Input resistance 50 Ω)
Voltage
0 – 10 V DC (Input resistance 200 kΩ min.)
2 – 10 V DC (Input resistance 200 kΩ min.)
0 – 5 V DC (Input resistance 100 kΩ min.)
1 – 5 V DC (Input resistance 100 kΩ min.)

OUTPUT – Field-selectable

Current
4 – 20 mA DC (Load resistance 550 Ω max.)
0 – 20 mA DC (Load resistance 550 Ω max.)
Voltage
0 – 10 V DC (Load resistance 10 kΩ min.)
2 – 10 V DC (Load resistance 10 kΩ min.)
0 – 5 V DC (Load resistance 5000 Ω min.)
1 – 5 V DC (Load resistance 5000 Ω min.)

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: Options other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

GENERAL SPECIFICATIONS

Connection
Input and output: Spring clamp terminal
Power input: Via the power connector or the spring clamp terminal
Applicable wire size: 0.2 to 1.5 mm2, stripped length 8 mm
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Zero adjustment: -2 to +2 % (front)
Span adjustment: 98 to 102 % (front)
Power indicator LED: Green LED turns on when the power is supplied.

INPUT SPECIFICATIONS

DC Current: Input resistor incorporated

INSTALLATION

Power consumption: Max. 0.6 W
Power input: Max. 3 A (Total current consumed by the interconnected signal conditionerse must be 3 A or less.)
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 65 g (2.3 oz)

PERFORMANCE in percentage of span

Accuracy: ±0.1 %
I/O setting accuracy: ±0.2 %
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F)
Response time (0 – 90 %): selectable with DIP SW 
Standard: ≤ 500 msec.
Fast: ≤ 5 msec.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @1 minute  (input to output to power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

Refer to the instruction manual for the setting procedure.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM