ES-2459 Rev.1

M5PP

Super-mini Terminal Block Signal Conditioners M5-UNIT

PULSE ISOLATOR

Functions & Features
• Galvanically isolates pulse rate signals
• Input frequency = output frequency
• Various outputs (open collector and voltage pulse)
• Power LED

MODEL: M5PP–[1][2][3]–R[4]

ORDERING INFORMATION

• Code number: M5PP-[1][2][3]-R[4]
Specify a code from below for each of [1] through [4].
  (e.g. M5PP-BMN-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] INPUT

A1: Open collector (max. 10 kHz)
A2: Mechanical contact (max. 30 Hz)
B: Voltage pulse (max. 10 kHz)
I: Clamp-on pulse sensor CLSP

[2] OUTPUT

A1: High frequency open collector (max. 10 kHz)
A2: Low frequency open collector (max. 30 Hz)
M: 5 V pulse (max. 10 kHz)
N: 12 V pulse (max. 10 kHz)
P: 24 V pulse (max. 10 kHz)

[3] OUTPUT LOGIC

N: The same as the input
R: Inverted

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[4] OPTIONS

blank: none
/Q: Options other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

RELATED PRODUCTS

• Clamp-on pulse sensor (model: CLSP)

GENERAL SPECIFICATIONS

Construction: Terminal block
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Frequency range: Input and output are the same.
Chattering protection: Filter provided for mechanical contact input
Power indicator LED: Green LED turns on when the power is supplied.
Input pulse sensing: DC coupled

INPUT SPECIFICATIONS

Excitation: 12 V DC @30 mA; shortcircuit protection
Open Collector
Maximum frequency
: 10 kHz
Pulse width time requirement: 10 μsec. min. for ON and OFF
Sensing: Approx. 12 V DC @3 mA
ON/OFF level: ≤ 600 Ω / 1.8 V for ON, ≥ 100 kΩ / 3.5 V for OFF
Mechanical Contact
Maximum frequency
: 30 Hz
Pulse width time requirement: 10 msec. min. for ON and OFF
Sensing: Approx. 12 V DC @3 mA
ON/OFF level: ≤ 200 Ω / 0.6 V for ON, ≥ 100 kΩ / 2.5 V for OFF
Voltage Pulse
Maximum frequency: 10 kHz
Pulse width time requirement: 10 μsec. min. for high and low levels
Waveforms: Square or sine
Hi/Lo level: 2 – 50 V DC for high level; ≤1 V DC for low level
Input impedance: 10 kΩ min.
Clamp-on Pulse Sensor CLSP
Maximum frequency: 50 000 pulses/hour
ON/OFF level: ≤ 400 Ω / 1.3 V for ON, ≥ 200 kΩ / 12 V for OFF

OUTPUT SPECIFICATIONS

High Frequency Open Collector:
50 V DC @100 mA (resistive load)
Maximum frequency: 10 kHz
Saturation voltage: 0.5 V DC
Low Frequency Open Collector:
50 V DC @100 mA (resistive load)
Maximum frequency: 30 Hz
Timer: Limits ≥ 75 msec. within 75 ±25 msec.
    ON time for output logic non-inverted
    OFF time for output logic inverted
Saturation voltage: 0.5 V DC
Voltage Pulse
Maximum frequency: 10 kHz
High level: Rating (5, 12 or 24 V) ±10 %
Low level: ≤ 0.5 V
Load resistance:
≥ 1.0 kΩ for 5 V
≥ 2.4 kΩ for 12 V
≥ 4.8 kΩ for 24 V

INSTALLATION

Power consumption
DC: Approx. 1.5 W
Operating temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: DIN rail
Weight: 80 g (2.8 oz)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output to power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
UK conformity (UKCA):
The UK legislations and designated standards are equivalent to the applicable EU directives.
(Refer to our website for more information about the legislations and designated standards.)

FRONT VIEW

OUTPUT LOGIC

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM