·Some details are not shown. Please refer to specification sheets for all information.

18TG

Rack-mounted DCS Signal Conditioners 18-RACK

TACHOGENERATOR CONVERTER

Functions & Features
• Converting an AC voltage from a tachogenerator (tachometer) into two standard process signals
• Second channel output available at the front terminals and at the Standard Rack connector
Typical Applications
• Measuring rotating or moving speed of multispeed motors, belt conveyers, metering pumps
 

MODEL: 18TG–[1]66–R

ORDERING INFORMATION
• Code number: 18TG-[1]66-R
Specify a code from below for [1]
(e.g. 18TG-166-R)
Special input range (For code U)

[1] INPUT
Voltage
1: 0 – 35 V AC (Input resistance 200 kΩ min.)
U: Specify voltage (0 % input must be 0 V.)

OUTPUT 1
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)

OUTPUT 2
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)

POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw terminals on the front and connector on the rear; terminal cover provided
Connection
  Input
: M3.5 screw terminals (torque 0.8 N·m)
  Output 1: Connector
  Output 2: M3.5 screw terminals (torque 0.8 N·m)
  and connector
  Power input: Supplied from connector
Screw terminal: Nickel-plated steel
Isolation: Input to output 1 to output 2 to power
Overrange output: 0 to 120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)

INPUT SPECIFICATIONS
Input: 0 – 250 V AC
Minimum span: 50 mV
Input resistance: 200 kΩ minimum
Frequency: 100 Hz min., 1 kHz max. with 100 % input

INSTALLATION
Power consumption
DC: Approx. 35 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 18BXx or 18KBXx
Weight: 150 g (0.33 lbs)

PERFORMANCE in percentage of span
Accuracy: ±0.2 % (excluding ≤ 15 Hz)
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Ripple: 0.5 %p-p max. (100/120 Hz)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input to output 1 or output 2 or power)
500 V AC @ 1 minute
(output 1 to output 2 to power)
1500 V AC @ 1 minute
(input or output or power to ground)

DIMENSIONS unit: mm (inch)

TERMINAL ASSIGNMENTS

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG Co., Ltd.