ES-6040 Rev.3

M1EXV-4

Multi-channel Super-mini Signal Conditioners
with Display M1E-4 Series

SIGNAL TRANSMITTER

(4 channels, PC programmable)
Functions & Features
• Converts DC input from a sensor into a standard process signal
• 4 channels
• Isolation between inputs and outputs
• Adjustments with the front buttons
• OEL display with good visibility
• Linearization available for each channel (111 points)
Typical Applications
• Isolation between control room and field instrumentation
• Ideal for quick spare part
 

MODEL: M1EXV-4-R[1]

ORDERING INFORMATION

• Code number: M1EXV-4-R[1]
Specify a code from below for [1].
  (e.g. M1EXV-4-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01/SET)

NO. OF CHANNELS

4: 4 channels

INPUT – Field-selectable

◆ DC Input
Current input: 0 - 20 mA DC
Voltage input: -5 - +5 V DC
Voltage input: -10 - +10 V DC

OUTPUT – Field-selectable

◆ DC Output
Current output: 0 - 20 mA DC
• Voltage output: -5 - +5 V DC
• Voltage output: -10 - +10 V DC

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
 (No. ESU-6040)

RELATED PRODUCTS

• Installation base (model: M1E-BS2)
• M1E configurator software (model: M1ECFG (M1E4CFG))
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual (EM-6041) for the M1E configurator for applicable cable types.

PACKAGE INCLUDES...

• Precision resistor module (model: REM3-250): 4

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
• Connected to base with connector
• Base
 M2.6 screw terminals (torque: 0.5 N·m)
 Applicable solderless terminal size (M3)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Isolation: Ch1 input to ch2 input to ch3 input to ch4 input to ch1 output to ch2 output to ch3 output to ch4 output to power
Overrange output: Approx. -5 to +105 % (Not available for current output not greater than 0 mA)
Zero fine adjustment: -5 to +5 % (front button)
Span fine adjustment: 95 to 105 % (front button)
Configuration: Program with front buttons or Via PC.
Programmable features include: Refer to the parameter list.
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
■Recommended solderless terminal size - M3 (unit: mm)

DISPLAY

Display functions: Displays and sets measured range, engineering unit
Display size: Approx. 15.6 × 20.8 mm (0.61” × 0.82”)
Number of pixels: 68 × 95 (horizontal × vertical)
Character color: Yellow
Display life: Approx. 40000 hours
(Expected time for the Display brightness to be reduced to 50 % when the Display is used continuously with brightness setting 2 in 25 ℃)
Display type: OEL display
Display digit: Negative 5 digits, positive 6 digits (-99999 to 999999)
Decimal point position: Selectable

INPUT SPECIFICATIONS

DC Current
Input resistance
: Precision resistor module (0.5 W) provided
Input range: 0 - 20 mA DC
Minimum span: 1 mA
The measurement available for -5 - +105% of input setting range.
DC Voltage
Narrow Spans (mV)
  Input range: -5 – +5 V DC
  Minimum span: 250 mV
Wide Spans (V)
  Input range: -10 – +10 V DC
  Minimum span: 1 V
Input resistance: 1 MΩ minimum
The measurement available for -5 - +105% of input setting range.

OUTPUT SPECIFICATIONS

■ DC Current
Output range: 0 – 20 mA DC
Conformance range: 0 – 21mA DC
Minimum span: 1 mA
Load resistance: Output drive 15 V max.
(e.g. 4 – 20 mA: 750 Ω [15 V ÷ 20 mA])
(Not available to output less than 0 mA, output range may not be extended to -5 %)
DC Voltage
•Narrow Spans (mV)
 Output range
: -5 - +5 V DC
 Conformance range: -5.5 - +5.5 V DC
 Minimum span: 250 mV
•Wide Spans (V)
 
Output range: -10 - +10 V DC
 Conformance range: -11 - +11 V DC
 Minimum span: 1 V
Load resistance: 10 kΩ min.

INSTALLATION

Power consumption
DC: ≤ 5 W
Operating temperature: -5 to +55°C (23 to 131°F)
Storage temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 10 to 85 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 130 g (0.29 lb) except base

PERFORMANCE

Accuracy: Input accuracy + output accuracy
input accuracy + (output accuracy × segment gain) when segment gain > 1
See CALCULATION EXAMPLES OF OVERALL ACCURACY.
Inversely proportional to the setting span.
Input accuracy: (% of max. input range): ±0.03 %
Display accuracy
 Input display: Input accuracy ±1 digit
 Output display: Input accuracy + output accuracy ±1 digit
Output accuracy: (% of max. output range)
0 - 20 mA: ±0.06 %
-5 - +5 V: ±0.03 %
-10 - +10 V: ±0.03 %
Temp. coefficient (% of max. I/O range): ±0.015 %/°C (±0.008 %/°F)
Response time (filter time constant: 0 sec.): ≤ 0.5 sec.
(0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(Ch1 input to ch2 input to ch3 input to ch4 input to
ch1 output to ch2 output to ch3 output to ch4 output to power to ground)

CALCULATION EXAMPLES OF OVERALL ACCURACY

[Example] Input signal: 1 - 5 V DC, Output signal: 4 -
20 mA DC, Max segment gain with linearization set: 1.5
Input Range -5 – +5 V, Input Setting 1 – 5 V, Output Range 0 – 20 mA, Output Setting 4 – 20 mA, Segment Gain 1.5
Overall accuracy
• Input Accuracy = Input Range Span (10 V) ÷ Input Span
(4 V) × 0.03 % = 0.075 %
• Output Accuracy = Output Range Span (20 mA) ÷ Output Span (16 mA) × 0.06 % × Segment Gain (1.5) = 0.1125 %
Overall Accuracy = 0.075 + 0.1125 = ±0.1875 %

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

Refer to the operating manual (EM-6040-B) for detailed procedures of parameter settings.

TERMINAL ASSIGNMENTS

* Base does not come with the unit. Please order separately.

PARAMETER LIST

EXTERNAL DIMENSIONS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

* Mounting requirements for base.

TERMINAL ASSIGNMENTS unit: mm [inch]

* Base does not come with the unit. Please order separately.

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM