ES-3562 Rev.8
KP
Plug-in Signal Conditioners K-UNIT
PT TRANSMITTER
(Average sensing, RMS calibrated)
Functions & Features
• Converting an alternating voltage from a potential (voltage) transformer into a standard process signal
• Minimum ripple
• Isolation up to 2000 V AC
• High-density mounting
Typical Applications
• Centralized monitoring and control of power line and power supply voltages measured at switch boards
• Monitoring abnormal voltage drops for detecting overload
MODEL: KP–[1][2]–[3][4]
ORDERING INFORMATION
• Code number: KP-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. KP-1A-B/Q)
• Special output range (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] INPUT
Voltage
1
: 0 – 110 V AC
2
: 0 – 220 V AC
5
: 0 – 150 V AC
6
:
0 - 300 V AC
[2] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 600 Ω max.)
B
: 2 – 10 mA DC (Load resistance 1200 Ω max.)
C
: 1 – 5 mA DC (Load resistance 2400 Ω max.)
D
: 0 – 20 mA DC (Load resistance 600 Ω max.)
E
: 0 – 16 mA DC (Load resistance 750 Ω max.)
F
: 0 – 10 mA DC (Load resistance 1200 Ω max.)
G
: 0 – 1 mA DC (Load resistance 12 kΩ max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
1
: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2
: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3
: 0 – 1 V DC (Load resistance 100 Ω min.)
4
: 0 – 10 V DC (Load resistance 1000 Ω min.)
5
: 0 – 5 V DC (Load resistance 500 Ω min.)
6
: 1 – 5 V DC (Load resistance 500 Ω min.)
4W
: -10 – +10 V DC (Load resistance 2000 Ω min.)
0
: Specify voltage (See OUTPUT SPECIFICATIONS)
[3] AUXILIARY POWER SUPPLY
AC Power
B
: 100 V AC
C
: 110 V AC
D
: 115 V AC
F
: 120 V AC
G
: 200 V AC
H
: 220 V AC
J
: 240 V AC
DC Power
R
: 24 V DC
V
: 48 V DC
P
: 110 V DC
[4] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to auxiliary power
Input waveform
: Sine wave
Overrange output
: 0 to 120 % at 1 – 5 V
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
INPUT SPECIFICATIONS
Frequency
: 50 or 60 Hz
Input burden
: 1 VA
Overload capacity
: 150 % of rating for 10 sec., 120 % continuous
Operational range
: 0 – 120 % of rating
OUTPUT SPECIFICATIONS
■ DC Current
: 0 – 20 mA DC
Minimum span
: 1 mA
Offset
: Max. 1.5 times span
Load resistance
: Output drive 12 V max.
■
DC Voltage
: -10 – +12 V DC
Minimum span
: 5 mV
Offset
: Max. 1.5 times span
Load resistance
: Output drive 10 mA max.; 5 mA for negative voltage output; at ≥ 0.5 V
INSTALLATION
Auxiliary power supply
•
AC
: Operational voltage range: rating -15/+10 %,
50/60 Hz, approx. 2 VA
•
DC
: Operational voltage range: rating ±10 %,
or 85 – 150 V for 110 V rating, ripple 10 %p-p max.,
approx. 2 W (18 mA at 110 V)
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 85 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 350 g (0.77 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.2 % (at 23°C ±10°C or 73.4°F ±18°F, 45 – 65 Hz)
Response time
: ≤ 1 sec. (0 – 100 % ±1 %)
Ripple
: 0.5 %p-p max.
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute
(input to output to auxiliary power to ground)
Impulse withstand voltage
: 1.2 / 50 μsec., ±5 kV
(input to output or ground)
CONNECTION DIAGRAM
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]