ES-3832 Rev.3
BX-16G
STANDARD RACK MOUNTING FRAME
Functions & Features
• Standard Rack Mounting Frame for mounting individual housing-stored Space-saving Rack-mounted Signal Conditioners (M-RACK, H-RACK, W-RACK, B-RACK, A-RACK)
• Convenient for power supply wiring in instrumentation panels
• Can be inserted into JIS and EIA standard racks
• Also available with power distributor
• Power distributor has an alarm fuse in each loop
• Capable of alarm contact output for blown fuses
MODEL: BX–16G–[1]
ORDERING INFORMATION
• Code number: BX-16G-[1]
Specify a code from below for [1].
(e.g. BS-16G-B)
[1] Power distributor
1
: Without
2
: With (single-pole fuse)
B
: With (double-pole fuse)
GENERAL SPECIFICATIONS
Construction
: Rack-mounted
Capacity
:
16 positions (H-RACK, B-RACK)
8 positions (M-RACK, W-RACK, A-RACK)
Terminal screw material
:
Nickel-plated iron, torque: 0.8 N·m (with power distributor)
Material
: SPCC
Coating
: Melamine baked coating
Isolation
: Power to alarm (when power distributor is attached)
Power distributor circuit
: with alarm fuse for each single loop
Alarm
: dry contact output at blown fuse
Fuse rating
: 0.5 A
INSTALLATION
■
Power distributor
Power input
: Operational voltage range 24 V DC ± 10%
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Rack mounting
Weight
: Mounting frame approx. 800 g (1.8 lb), mounting frame + with power distributor approx. 2 kg (4.4 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
:
1500 V AC @1 minute (power supply or alarm terminal to ground)
500 V AC @1 minute (power supply to alarm terminal)
(BX-16G-2, B only)
CONNECTION DIAGRAM
■ WITH POWER DISTRIBUTOR Single-pole fuse
■ WITH POWER DISTRIBUTOR Double-pole fuse
EXTERNAL DIMENSIONS unit: mm [inch]
■ WITHOUT POWER DISTRIBUTOR
■ WITH POWER DISTRIBUTOR Single-pole fuse
■ WITH POWER DISTRIBUTOR Double-pole fuse
MOUNTING REQUIREMENTS unit: mm [inch]
■ WITHOUT POWER DISTRIBUTOR
■ WITH POWER DISTRIBUTOR