ES-4216 Rev.7

6DVI

Field-mounted Two-wire Signal Conditioners 6-UNIT

4-DIGIT LOOP POWERED INDICATOR

(intrinsically safe)
Functions & Features
• 4-digit LED display
• No external power source needed
• Scaling, linearization and other configurations selectable via three front control buttons
• Mountable on top of the Two-wire Universal Temperature Transmitter (model: 27HU)
Note: Differences between the 6DV and the 6DVI exist only in safety parameters. Refer to the relevant section for more information.

MODEL: 6DVI–[1]

ORDERING INFORMATION

• Code number: 6DVI-[1]
Specify a code from below for [1].
  (e.g. 6DVI-2)
• Use Ordering Information Sheet (No. ESU-4221). Factory standard setting will be used if not otherwise specified.
• Specify the country in which the product is to be used with the Safety Approval code 2.

[1] SAFETY APPROVAL

1: FM intrinsically safe
2: ATEX intrinsic safety

RELATED PRODUCTS

• DIN rail mounting adaptor (model: A-34)
• Mounting spacer (model: A-6)

GENERAL SPECIFICATIONS

Connection: Euro type terminal
Applicable wire size: 0.14 – 1.5 mm2 (AWG26 – 16), stripped length 6 mm
Housing material: Flame-resistant resin (black)
Linearization: Proportional, SQRT (X1/2), RT32 (X3/2), RT52 (X5/2), user’s linearization table (max. 21 calibration points)
(Default setting: Proportional)
A/D conversion: Dual-slope integration
Security: Protecting settings
Scaling: Programming via the front buttons

DISPLAY

LED: 8 mm (.3”) 7-segment, red
Number of display digits: 4
Scaling range: -1999 to 9999 counts
Offset range: -1999 to 9999 counts
Decimal point position: 10-1, 10-2, 10-3 or none
Polarity sign: Minus (–) sign added automatically according to the computation result
Over-range warning: All segments dark except the top ones that blink with the input exceeding the display/measurable range; or the bottom ones that blink with the input below the range.
Read rate: 2.5/s
Engineering unit indication: Sticker label attached
DC, AC, W, ℃ , °F, V, mV, A, mA, %, kW, mW, kV, kA, psi, K, bar, barg, Nℓ/min, kvar, Mvar, var, m, mm, kg, kg/h, kPa, MPa, N·m, Nm3/h, m3/h, m3/sec, m/sec, kgf/cm2, ℓ/min, %RH, ℓ, ℓ/h, t/h, rpm, ppm, pH, Pa

INPUT SPECIFICATIONS

DC Current: 4 – 20 mA DC
Measurable range: 3.75 – 23 mA DC
Maximum input current: Refer to ‘Safety Parameters.’
Voltage drop: Approx. 3.7 V with 4 mA
Approx. 4.0 V with 20 mA (Equivalent input impedance: Approx. 200 Ω)
(The minimum required supply voltage to the 2-wire transmitter added with the indicator’s voltage drop at the maximum input current must be within the output voltage range of the 2-wire transmitter’s excitation supply.)

INSTALLATION

Operating temperature: Refer to the 'Safety Parameters' section.
Operating humidity: 0 to 95 %RH (non-condensing)
Weight: 65 g (2.3 oz)

PERFORMANCE

Accuracy: ±0.01 mA
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) at 4 – 20 mA input

HOW TO CALCULATE ACCURACY AGAINST SCALE

Example 1: 4 – 20 mA input, Scale 0 – 100
Accuracy = 0.01 mA ÷ (20 – 4)mA × 100 = 0.063 %
Display Error = (100 – 0) × 0.063 % = ±0.063 digits
Example 2: 10 – 20 mA input, Scale 100 – 1000
Accuracy = 0.01 mA ÷ (20 – 10)mA × 100 = 0.1 %
Display Error = (1000 – 100) × 0.1 % = ±0.9 digits

STANDARDS & APPROVALS

Refer to the manuals to comply with the standards.
EU conformity:
ATEX Directive  (for ATEX intrinsic safety)
  Ex ia EN 60079-11
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
Safety approval:
FM: Intrinsically safe
  Class I, Div. 1, Groups A, B, C and D
  Class I, Zone 0, AEx ia IIC (US)
  Class I, Zone 0, Ex ia IIC (Canada)
  T4 and T5
  (Class 3600)
  (Class 3610)
  (ANSI/ISA 60079-0)
  (ANSI/ISA 60079-11)
  (CAN/CSA-C22.2 E60079-0)
  (CAN/CSA-C22.2 E60079-11)

SAFETY PARAMETERS

Operating temperature
Temp. class: Operating temperature
  T4: -40 to +85°C
  T5: -40 to +60°C
Intrinsic safety Ex data
  Ui
: (Vmax) 28 V DC
  Ii: (Imax) 120 mA DC (Max. current allowed for the
  safety approval; Not to guarantee the product’s
  performance.)
  Pi: (Pmax) 0.84 W
  Ci: 1.0 nF
  Li: 0 mH

DISPLAY DESCRIPTIONS

DISPLAY DIGITS
The decimal point position may shift according to the required number of digits for the integer section, even when more than one decimal places have been specified.
However, when the number of decimal places is set to 3, the ‘0’ in the integer section is not shown in order to secure the number of effective digits, as explained in the table below.
The ‘0’ is displayed when the number of decimal places is set to 2, though the number of effective digits in this case is reduced by 1 digit compared from the 3 decimal places.
Select appropriately for the application. Refer to ‘Programming Procedure’ for how to choose decimal point positions.

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

CONNECTION DIAGRAM