ES-4220 Rev.21

6DV-B

Field-mounted Two-wire Signal Conditioners 6-UNIT

4-DIGIT LOOP POWERED INDICATOR

(outdoor enclosure, intrinsically safe/explosion-proof)
Functions & Features
• 4-digit LED display
• No external power source needed
• Scaling, linearization and other configurations selectable via three front control buttons
• Stainless steel enclosure optional
Note: Differences between the 6DV-B and the 6DVI-B exist only in safety parameters.  Refer to the relevant section for more information.

MODEL:6DV–B–[1][2][3][4][5]

ORDERING INFORMATION

• Code number: 6DV-B-[1][2][3][4][5]
Specify a code from below for each of [1] through [5].
 (e.g. 6DV-B-0T01/S)
• Use Ordering Information Sheet (No. ESU-4220). Factory standard setting will be used if not otherwise specified.
• Specify the country in which the product is to be used with the Safety Approval code 2 or 4.

[1] SAFETY APPROVAL

0: None
1: FM intrinsically safe
2: ATEX intrinsic safety
3: FM explosion-proof
4: ATEX flameproof
7: TIIS intrinsic safety (CE not available)
8: TIIS flameproof (CE not available)
Confirm selectable combinations of approval and wiring conduit types in the table.

[2] TERMINAL BLOCK

0: None (Euro type terminal block at the rear of indicator module)
(TIIS flameproof or TIIS intrinsically safe approvals not selectable)
T: Incorporated

[3] WIRING CONDUIT

0: G 1/2
1: 1/2 NPT
2: M20 × 1.5
3: PG 13.5
Confirm selectable combinations of approval and wiring conduit types in the table.

[4] MOUNTING BRACKET

0: Without
1: With

[5] OPTIONS

Enclosure Materials
Blank: Diecast aluminium enclosure
/S: Stainless steel enclosure
(TIIS flameproof approval not selectable)

RELATED PRODUCTS

• Cable gland (model: BX-E-SXY)
• Stopping plug (model: BX-E-SBP)

PACKAGE INCLUDES...

Cable gland: Two provided for TIIS flameproof type
  Model No.: BX-E-SXY
  Cable entries: Elastomeric sealing rings
  Wiring conduit size: G 1/2
  Material: Chrome-plated brass (entry)
  CR (sealing ring)
  Applicable wire size: 8 - 12 dia.
Stopping plug: One provided for TIIS flameproof type
  Model No.: BX-E-SBP
  Wiring conduit size: G 1/2
  Material: Diecast aluminium (plug)
  NBR (O-ring)
• Mounting screws
    Bolt (M8 x 15): 4 pcs.
    Spring washer for M8: 4 pcs.
Mounting bracket assembly (option)
    Mounting bracket: 1
    M10 U-bolt: 2
    Nut for M10: 4
    Spring washer for M10: 4
  Material:  Stainless steel 304 (for aluminum enclosure)
                 Stainless steel 316 (for stainless steel enclosure)
  Applicable pipe: 1 1/2” min.; 2” max.
Engineering unit label (1)

GENERAL SPECIFICATIONS

Degree of protection: NEMA 4X, IP66/IP67
Wiring conduit: See ‘Ordering information.’
Electrical connection:
Without terminal block: Euro terminal block (Applicable wire size: 0.14 – 1.5 mm(AWG26 – 16), stripped length 6 mm) 
With terminal block:
M3 screw terminal (torque 0.5 N·m)
Screw terminal:
With terminal block: Nickel-plated steel
Materials
  Meter housing: Flame-resistant resin (black)
  Enclosure: Diecast aluminium standard; stainless steel casting optional (equivalent to type 316); silver color, epoxy resin coated
Isolation: Input to outdoor enclosure
Linearization: Proportional, SQRT (X1/2), RT32 (X3/2), RT52 (X5/2), user’s linearization table (max. 21 calibration points)
(Default setting: Proportional)
A/D conversion: Dual-slope integration
Security: Protecting settings
Scaling: Programming via the front buttons

DISPLAY

LED: 8 mm (.3”) 7-segment, red
Number of display digits: 4
Scaling range: -1999 to 9999 counts
Offset range: -1999 to 9999 counts
Decimal point position: 10-1, 10-2, 10-3 or none
Polarity sign: Minus (–) sign added automatically according to the computation result
Over-range warning: All segments dark except the top ones that blink with the input exceeding the display/measurable range; or the bottom ones that blink with the input below the range.
Read rate: 2.5/s
Engineering unit indication: Sticker label attached
DC, AC, W, ℃ , °F, V, mV, A, mA, %, kW, mW, kV, kA, psi, K, bar, barg, Nℓ/min, kvar, Mvar, var, m, mm, kg, kg/h, kPa, MPa, N·m, Nm3/h, m3/h, m3/sec, m/sec, kgf/cm2, ℓ/min, %RH, ℓ, ℓ/h, t/h, rpm, ppm, pH, Pa

INPUT SPECIFICATIONS

DC Current: 4 – 20 mA DC
Measurable range: 3.75 – 23 mA DC
Maximum input current
Non-approved
: 100 mA
Explosion-proof: 23 mA
Intrinsically safe: Refer to ‘Safety Parameters.’
Voltage drop: Approx. 3.7 V with 4 mA
Approx. 4.0 V with 20 mA (Equivalent input impedance: Approx. 200 Ω)
The minimum required supply voltage to the 2-wire transmitter added with the indicator’s voltage drop at the maximum input current must be within the output voltage range of the 2-wire transmitter’s excitation supply.

INSTALLATION

Operating temperature: -40 to +85°C (-40 to +185°F)
(See Safety Parameters for use in a hazardous location.)

Weight
· Unit
  Approx. 1.3 kg (2.9 lb), aluminium
  Approx. 4.0 kg (8.8 lb), stainless steel
  Approx. 2.0 kg (4.4 lb), TIIS flameproof
· Mounting bracket set (option)
  Approx. 0.78 kg (1.72 lb)

PERFORMANCE

Accuracy: ±0.01 mA
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) at 4 – 20 mA input
Dielectric strength: 1500 V AC @ 1 minute
(input to outdoor enclosure)

HOW TO CALCULATE ACCURACY AGAINST SCALE

Example 1: 4 – 20 mA input, Scale 0 – 100
Accuracy = 0.01 mA ÷ (20 – 4)mA × 100 = 0.063 %
Display Error = (100 – 0) × 0.063 % = ±0.063 digits
Example 2: 10 – 20 mA input, Scale 100 – 1000
Accuracy = 0.01 mA ÷ (20 – 10)mA × 100 = 0.1 %
Display Error = (1000 – 100) × 0.1 % = ±0.9 digits

STANDARDS & APPROVALS

Refer to the manuals to comply with the standards.
EU conformity:
ATEX Directive 
  Ex ia EN 60079-11 (for ATEX intrinsic safety)
  Ex d EN 60079-1 (for ATEX flameproof)
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
Safety approval:
FM: Intrinsically safe (US, Canada)
  Class I, Div. 1, Groups A, B, C and D
  Class II, Div. 1, Groups E, F and G
  Class III, Div. 1
  Class I, Zone 0, AEx ia IIC (US)
  Class I, Zone 0, Ex ia IIC (Canada)
  T4 and T5
  (Class 3600)
  (Class 3610)
  (ANSI/ISA 60079-0)
  (ANSI/ISA 60079-11)
  (CAN/CSA-C22.2 E60079-0)
  (CAN/CSA-C22.2 E60079-11)
FM: Explosion-proof and Dust-ignition proof (US)
  Class I, Div. 1, Groups B, C and D
  Class II, Div. 1, Groups E, F and G
  Class III, Div. 1
  T6
  (Class 3600)
  (Class 3615)
TIIS: Intrinsic safety
  Ex ia IIC T5
TIIS: Flameproof
  Ex d IIC T6

SAFETY PARAMETERS

Operating temperature
For FM/ATEX Intrinsically safe
  (Temp Class: Operating temperature)
  T4: -40 to +80°C
  T5: -40 to +60°C
FM Explosion-proof
  T6: -40 to +80°C
ATEX Flameproof
  T5: -40 to +80°C
  T6: -40 to +70°C
For TIIS Intrinsically safe
  T5 -20 to +60°C
For TIIS Flameproof
  T6 -20 to +60°C
Ex-data:
  Ui (Vmax): 30 V DC
  Ii (Imax): 100 mA DC
  Pi (Pmax): 0.75 W
  Ci: 1.0 nF
  Li: 0 mH (TIIS Intrinsically Safe: ‘Negligible value’)

DISPLAY DESCRIPTIONS

DISPLAY DIGITS
The decimal point position may shift according to the required number of digits for the integer section, even when more than one decimal places have been specified.
However, when the number of decimal places is set to 3, the ‘0’ in the integer section is not shown in order to secure the number of effective digits, as explained in the table below.
The ‘0’ is displayed when the number of decimal places is set to 2, though the number of effective digits in this case is reduced by 1 digit compared from the 3 decimal places.
Select appropriately for the application. Refer to ‘Programming Procedure’ for how to choose decimal point positions.

EXTERNAL VIEW (indicator module)

■ FRONT VIEW
■ REAR VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

CONNECTION DIAGRAM