ES-8869 Rev.4

6BSN

Field-mounted Two-wire
Signal Conditioners 6B-UNIT

INPUT LOOP POWERED ISOLATOR

Functions & Features
• IP66 / IP67 housing enables field mounting
• Stainless steel field housing selectable
• Isolator not requiring power supply with input 4 to 20 mA DC / 10 to 50 mA DC, output 4 to 20 mA DC

MODEL: 6BSN-0[1][2][3][4]

ORDERING INFORMATION

• Code number: 6BSN-0[1][2][3][4]
Specify a code from below for each of [1] through [4].
  (e.g. 6BSN-0A0A1)

SAFETY APPROVAL

0: None

[1] INPUT

A: 4 – 20 mA DC
H: 10 – 50 mA DC

[2] WIRING CONDUIT

0: G 1/2
1: 1/2 NPT
2: M20 × 1.5
3: PG 13.5

[3] ENCLOSURE MATERIAL

A: Diecast aluminum
S: Stainless steel casting

[4] MOUNTING BRACKET

0: Without
1: With

PACKAGE INCLUDES...

• Mounting screws
    Bolt (M8 x 15): 4
    Spring washer for M8: 4
  Material: Stainless steel 304
• Mounting bracket assembly (option):
    Mounting bracket: 1
    M10 U-bolt: 2
    Nut for M10: 4
    Spring washer for M10: 4
  Material: Stainless steel 304
  Applicable pipe: 1 1/2” min.; 2” max.

GENERAL SPECIFICATIONS

Degree of protection: NEMA 4X, IP66/IP67
Wiring conduit: See ‘Ordering information.’
Electrical connection: M3 screw terminals
(torque 0.6 N·m)
Materials
Transmitter housing: Diecast aluminum
   Screw terminals: Nickel-plated steel
Enclosure: Diecast aluminum or stainless steel casting (equivalent to type 316); silver color, epoxy resin coated
Isolation: Input to output to outdoor enclosure
Zero adjustment: -0.5 to +0.5 % (behind the access cover)
Span adjustment: 98.5 to 101.5 % (behind the access cover)

INPUT & OUTPUT

Input 4 – 20 mA DC / Output 4 – 20 mA DC
Equivalent input impedance
: 230 Ω + load resistance with 20 mA input
Operational range: 3 – 22 mA DC
(Accuracy is assured within 4 – 22 mA)
Load resistance: 350 Ω maximum; min. 50 Ω required for adequate operation
Input 10 – 50 mA DC / Output 4 – 20 mA DC
Equivalent input impedance
: 90 Ω + [load resistance x 0.16] with 50 mA input
Operational range: 7 – 55 mA DC
(Accuracy is assured within 8 – 55 mA)
Load resistance: 600 Ω maximum; min. 50 Ω required for adequate operation
•INPUT 4 – 20mA DC / OUTPUT 4 – 20 mA DC
•INPUT 10 – 50 mA DC / OUTPUT 4 – 20 mA DC

INSTALLATION

Operating temperature: -5 to +70°C (23 to 158°F)
Weight
• Unit
  Approx. 1.5 kg (2.9 lb), aluminium
  Approx. 4.2 kg (8.8 lb), stainless steel
• Mounting bracket assembly (option)
  Approx. 0.78 kg (1.72 lb)

PERFORMANCE in percentage of span

Accuracy: ±0.1 %
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)
Response time
  4 - 20 mA DC input: Approx. 45 msec. (0 – 90 %, 50 Ω load)
  10 - 50 mA DC input: Approx. 15 msec. (0 – 90 %, 50 Ω
  load)
Load effect (The unit is calibrated with 250 Ω load at the factory.)
4 – 20 mA input:
  0.015 %/Ω (50 – 150 Ω)
  0.003 %/Ω (150 – 350 Ω)
10 – 50 mA input
  0.015 %/Ω (50 – 100 Ω)
  0.003 %/Ω (100 – 600 Ω)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @1 minute
(input to output)
1500 V AC @1 minute (input or output to outdoor enclosure)

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM