ES-6612 Rev.4

60S

Field Network Modules 60-UNIT Series

ANALOG I/O MODULE

(Multiplex Transmission System)
Functions & Features
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with Multiplex Transmission System
• Saving power and I/O wiring inside an instrumentation panel

MODEL: 60S-16[1]-[2][3]

ORDERING INFORMATION

• Code number: 60S-16[1]-[2][3]
 Specify a code from below for each of [1] through [3].
  (e.g. 60S-161-K/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

NO. OF CHANNELS

16: 16 points

[1] I/O TYPE

1: Input
2: Output

[2] POWER INPUT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[3] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

RELATED PRODUCTS

•Special cable (model: MCN34)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
  SIN-NET,
RUN contact output: Euro type connector
  terminal (applicable wire size: 0.2 to 2.5 mm2, stripped
  length 7 mm)
  I/O: 34-pin connector (OMRON XG4A-3434)
  Power input: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: I/O to SIN-NET to RUN contact output to power to FG1
Power indicator: Red LED turns ON in normal conditions; OFF when the voltage level becomes low.
RUN indicator: Red LED turns ON when the selfdiagnosis proves normal, OFF in an abnormality.
RUN Contact Output: Contact opens at error
Rated load: 30 V DC @ 0.4 A (resistive load)
Maximum switching voltage: 125 V DC
Maximum switching power: 60 W
Minimum load: 10 mV DC @ 1 mA
Mechanical life: 5 x 107 cycles
Self-diagnosis
  Communication
: The receiver modules detect loss of communication and wire break.
  CPU: Watch-dog timer
  Memory: Sum check
  Power voltage: Detects when the voltage supply to the CPU drops.

COMMUNICATION

Configuration: Multi-drop
Standard: Conforms to EIA RS-422
Communication: 2-wire, half-duplex
Transmission speed: 125 kbps
Control procedure: SDLC
Data encoding: NRZ
Protocol: SIN-NET (dedicated protocol)
Error check: CRC
Transmission distance: 500 m
Transmission media: Twisted-pair cable CPEV-0.9 dia.
Station No.: Rotary switch
Terminator: Incorporated (remove jumper pin with those modules not located at the end of transmission line)

INPUT SPECIFICATIONS

Analog Input
Input range
: 1 – 5 V DC 
Input resistance: ≥ 1 MΩ
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.

OUTPUT SPECIFICATIONS

Analog Output
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held.
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.

INSTALLATION

Power consumption
AC: Approx. 4 VA
DC: Approx. 4 W (160 mA)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight: 450 g (0.99 lb)

PERFORMANCE in percentage of span

A/D conversion: ±0.1 %
D/A conversion: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or output to SIN-NET to RUN contact output to power)
2000 V AC @ 1 minute (input or output or SIN-NET or RUN contact output or power to FG1)

DESCRIPTIONS

RUN Contact Output (LED) Behaviors
Input module
The LED for the Input Modules turns ON when the network is on-line.
When there is an abnormality in the network, the LED turns OFF.
The network is reconfigured after an abnormality.
Output module
The LED for the Output Modules turns ON when the network is on-line and the module receives data from the corresponding Input Module.
When there is an abnormality in the network or there is no data receiving, the LED turns OFF.
Station Number (Address)
A) 1 input module and X output modules:
Match the address for input and output modules.
B) Computer interface:
Set address numbers to correspond with the computer as output module.
Transmission Time
Integrate all the transmission time for each process input module in the system.
•Analog input 16 points: 24.0 msec.
An analog module does not transmit all its signals in serial but does 1 point per each cycle.  For example, when 1 contact input module (DLA1, 32 points) and 1 analog input module (16 points) are connected, 32 point contact signal and 1 point analog signal are transmitted in turn.  One cycle time is therefore calculated as:
  32 points × 1.5 msec. + 24 msec. = 72 msec.
This method is beneficial for giving a priority to contact signals which vary rapidly.

Applicable models for use with 60S Input Module
• 60S-162 (Ao 16 points)
• DLA1-xM1 (Ao 32 points; only the top 16 out of 32 are used)

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM