ES-9311 Rev.14

48V

Bargraph Indicators 48 Series

BARGRAPH INDICATOR

Functions & Features
• Displaying a process variable in graphic bargraph of 101 LED segments
• Clear LED
• High-density mounting

MODEL: 48V–[1][2][3][4]-[5]

ORDERING INFORMATION

• Code number: 48V-[1][2][3][4]-[5]
Specify a code from below for each of [1] through [5].
  (e.g. 48V-2RRVA-R)
• Special input range (For codes Z & 0)
• Scale (e.g. 0 – 100 %)

[1] BARGRAPHS

1: Single
2: Dual

[2] LED COLOR

R: Red
Y: Amber
G: Green
Dual (left/right)
RR: Red / Red
YY: Amber / Amber
GG: Green / Green
RY: Red / Amber
RG: Red / Green
YR: Amber / Red
YG: Amber / Green
GR: Green / Red
GY: Green / Amber

[3] MOUNTING DIRECTION

V: Vertical
H: Horizontal

[4] INPUT

Current
A: 4 – 20 mA DC (Input resistance 10 Ω)
B: 2 – 10 mA DC (Input resistance 20 Ω)
C: 1 – 5 mA DC (Input resistance 39 Ω)
D: 0 – 20 mA DC (Input resistance 10 Ω)
E: 0 – 16 mA DC (Input resistance 12 Ω)
F: 0 – 10 mA DC (Input resistance 20 Ω)
G: 0 – 1 mA DC (Input resistance 200 Ω)
H: 10 – 50 mA DC (Input resistance 3.9 Ω)
Z: Specify current (See INPUT SPECIFICATIONS)
Voltage
3: 0 – 1 V DC (Input resistance 100 kΩ)
4: 0 – 10 V DC (Input resistance 330 kΩ)
5: 0 – 5 V DC (Input resistance 250 kΩ)
6: 1 – 5 V DC (Input resistance 250 kΩ)
0: Specify voltage (See INPUT SPECIFICATIONS)

[5] POWER INPUT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 63 Hz)
L: 170 – 264 V AC
(Operational voltage range 170 – 264 V, 47 –  63 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±15 %, ripple 10 %p-p max.)

GENERAL SPECIFICATIONS

Construction: Panel flush mounting
Connection: M3 screw terminals (torque 0.6 N·m)
Screw terminal: Chromated brass
Housing material: ABS resin
Isolation: Input 1 to input 2 to power
Scale plate: Aluminium (white scale & characters on black base)
Scale
Characters including decimal points:
  Max. 6 charac. (48V-1, vertical mount.)
  Max. 4 charac. (48V-2, vertical mount.)
  Max. 4 charac. (48V-1, horizontal mount.)
  Max. 4 charac. (48V-2, horizontal mount.)
Divisions: 22 – 54.9
Engineering unit:
  Max. 8 charac. (48V-1, vertical mount.)
  Max. 5 charac. (48V-2, vertical mount.)
  Max. 8 charac. (48V-1, horizontal mount.)
  Max. 3 charac. (48V-2, horizontal mount.)
  If there is only one engineering unit with dual bargraph
  type, the position and maximum number of characters
  for single type are applied.
Bargraph: 101-segment LED, 100 mm (3.96”) long, 1.5 mm (.06”) wide

INPUT SPECIFICATIONS

DC Current: 0 – 50 mA DC; input resistor incorporated
Minimum span: 1 mA
0 % input: 0 mA DC
DC Voltage: 0 – 10 V DC
Minimum span: 1 V
0 % input: 0 V DC

INSTALLATION

Power consumption
AC: Approx. 3.5 VA (single) or 5.5 VA (dual)
DC: Approx. 2 W (single) or 4 W (dual)
Operating temperature: 0 to 50°C (32 to 122°F)
Operating humidity: 40 to 80 %RH (non-condensing)
Mounting: Panel flush mounting
Weight:
  290 g (0.64 lb) for 48V-1, DC powered
  320 g (0.71 lb) for 48V-1, AC powered
  340 g (0.75 lb) for 48V-2, DC powered
  370 g (0.82 lb) for 48V-2, AC powered

PERFORMANCE in percentage of span

Accuracy: ±1 % ±1 digit
Response time: 0.5 sec.
Insulation resistance: ≥ 50 MΩ with 500 V DC
(input or power to ground)
Dielectric strength:
  2000 V AC @1 minute (input or power to ground)
  1500 V AC @ 1 minute (input to AC power)
  500 V AC @ 1 minute (input to DC power)
  500 V AC @ 1 minute (input 1 to input 2)

STANDARD SCALE & UNIT EXAMPLES

EXTERNAL VIEW

CONNECTION DIAGRAM

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

PANEL CUTOUT unit: mm