ES-9312 Rev.19

48AV

Bargraph Indicators 48 Series

BARGRAPH INDICATING ALARM

Functions & Features
• Displaying a process variable in graphic bargraph of 101 LED segments
• Clear LED
• Providing max. 4 alarm contact outputs
• Relays can be used with 110 V DC power
• Multi-color indicator

MODEL: 48AV–[1][2][3][4]-[5]

ORDERING INFORMATION

• Code number: 48AV-[1][2][3][4]-[5]
Specify a code from below for each of [1] through [5].
  (e.g. 48AV-4RVA-R)
• Special input range (For codes Z & 0)
• Scale (e.g. 0 – 100 %)
• Color pattern for multi-color indicator (e.g. pattern 2)

[1] ALARM OUTPUT

2: 2 points
4: 4 points

[2] BAR LED COLOR

R: Red
Y: Amber
G: Green
C: Multi-color (red, amber and green)

[3] MOUNTING DIRECTION

V: Vertical
H: Horizontal

[4] INPUT

Current
A: 4 – 20 mA DC (Input resistance 10 Ω)
B: 2 – 10 mA DC (Input resistance 20 Ω)
C: 1 – 5 mA DC (Input resistance 39 Ω)
D: 0 – 20 mA DC (Input resistance 10 Ω)
E: 0 – 16 mA DC (Input resistance 12 Ω)
F: 0 – 10 mA DC (Input resistance 20 Ω)
G: 0 – 1 mA DC (Input resistance 200 Ω)
H: 10 – 50 mA DC (Input resistance 5.1 Ω)
Z: Specify current (See INPUT SPECIFICATIONS)
Voltage
3: 0 – 1 V DC (Input resistance 100 kΩ)
4: 0 – 10 V DC (Input resistance 330 kΩ)
5: 0 – 5 V DC (Input resistance 250 kΩ)
6: 1 – 5 V DC (Input resistance 250 kΩ)
0: Specify voltage (See INPUT SPECIFICATIONS)

[5] POWER INPUT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 63 Hz)
L: 170 – 264 V AC
(Operational voltage range 170 – 264 V, 47 –  63 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±15 %, ripple 10 %p-p max.)

GENERAL SPECIFICATIONS

Construction: Panel flush mounting
Connection: M3 screw terminals (torque 0.6 N·m)
Screw terminal: Chromated brass
Housing material: ABS resin
Isolation: Input to output to power
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
Scale plate: Aluminium (white scale & characters on black base)
Scale
  Characters including decimal points
: Max. 4 characters
  Divisions: 22 – 54.9
  Engineering unit: Max. 8 characters
Setpoint adjustment
  2 points
:
  H: [L setpoint + 1 %] to 100 %
  L: 0 % to [H setpoint – 1 %]
  4 points:
  HH: [H setpoint + 1 %] to 100 %
  H: [L setpoint + 1 %] to [HH setpoint – 1 %]
  L: [LL setpoint + 1 %] to [H setpoint – 1 %]
  LL: 0 % to [L setpoint – 1 %]
Alarm deadband (hysteresis): 1 %
Bargraph: 101-segment LED, 100 mm (3.96”) long, 1.5 mm (.06”) wide

INPUT SPECIFICATIONS

DC Current: 0 – 50 mA DC; input resistor incorporated
Minimum span: 1 mA
0 % input: 0 mA DC
DC Voltage: 0 – 10 V DC
Minimum span: 1 V
0 % input: 0 V DC

OUTPUT SPECIFICATIONS

Alarm Output: Relay contact
Rated load: 125 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 2 A (resistive load)
Maximum switching voltage: 250 V AC or 220 V DC
Maximum switching power: 125 VA or 60 W
Minimum load: 10 mV DC @ 10 μA
Mechanical life: ≥ 108 cycles

INSTALLATION

Power consumption
AC: Approx. 5 VA  (7 VA for multi-color LED)
DC: Approx. 4 W (6 W for multi-color LED)
Operating temperature: 0 to 45°C (32 to 113°F)
Operating humidity: 40 to 80 %RH (non-condensing)
Mounting: Panel flush mounting
Weight: 590 g (1.30 lb)

PERFORMANCE in percentage of span

Accuracy: ±1 % ±1 digit
Setting accuracy: ±1 %
Response time: 0.5 sec.
Insulation resistance: ≥ 10 MΩ with 500 V DC (input to output to power)
Dielectric strength: 1500 V AC @ 1 minute
(input to power or ground)
1000 V AC @ 1 minute (power to ground, output to input or power or ground)

STANDARD SCALE & UNIT EXAMPLES

EXTERNAL VIEW

CONNECTION DIAGRAM

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

PANEL CUTOUT unit: mm