ES-2967 Rev.1
17RP
Rack-mounted Power Transducers 17-RACK
VAR TRANSDUCER
Functions & Features
• Providing a DC output signal in proportion to AC reactive power
• DC output containing little ripple is ideal for computer input
• "Time division multiplication" method accepts distorted waveforms
Typical Applications
• Centralized monitoring and control of power management system in a manufacturing facility or building
MODEL: 17RP–1[1][2]6–R
ORDERING INFORMATION
• Code number: 17RP-1[1][2]6-R
Specify a code from below for each of [1] and [2].
(e.g. 17RP-11P6-R)
• Var range (e.g. LAG 1000 – LEAD 1000 var)
CONFIGURATION
1
: 3-phase / 3-wire
[1] INPUT (unbalanced load)
(Voltage must be balanced.)
1
: 110 V / 5 A AC
2
: 110 V / 1 A AC
3
: 220 V / 1 A AC
4
: 220 V / 5 A AC
[2] OUTPUT SIGNAL POLARITY
P:
Negative in lag, positive in lead
M:
Negative in lead, positive in lag
OUTPUT
Voltage
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
AUXILIARY POWER SUPPLY
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
GENERAL SPECIFICATIONS
Construction
: Rack-mounted; terminal access via screw terminals on the front and connector on the rear; terminal cover provided
Connection
Input
: M3.5 screw terminals (torque 0.8 N·m)
Output
: Connector
Auxiliary power
: Supplied from connector
Screw terminal
: Nickel-plated steel
Isolation
: Voltage input to current input to output to auxiliary power
Computation
: Time division multiplication
Overrange output
: Approx. -10 to +120 %
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
INPUT SPECIFICATIONS
Frequency
: 50 or 60 Hz
• Voltage Input
Operational range
: 0 – 120 % of rating
Overload capacity
: 150 % of rating for 10 sec., 120 % continuous
• Current Input
Operational range
: 0 – 120 % of rating
Overload capacity
: 1000 % of rating for 3 sec., 200 % for 10 sec., 120% continuous
■
How To Determine Var Range
Calibration Range [var] = (Measuring Range) ÷
((VT Ratio) × (CT Ratio))
Check that the required calibration range is within the available range in the table.
[example]
3-phase / 3-wire, measuring range 75 kvar,
VT 220 / 110 V, CT 250 / 5 A
(75 × 10
3
[var])÷((220 ÷ 110) × (250 ÷ 5))= 750 [var]
OUTPUT SPECIFICATIONS
INSTALLATION
Auxiliary power supply
Current consumption
: Approx. 40 mA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 40 to 85 % RH (non-condensing)
Mounting
: Standard Rack 17BXE
Weight
: 200 g (0.44 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.5 % (at 23°C ±10°C or 73.4°F ±18°F,
45 – 65 Hz)
Response time
: ≤ 2 sec. (0 – 100 % ±1 %)
Ripple
: 1 %p-p max.
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 500 V AC @ 1 minute (output to auxiliary power)
2000 V AC @ 1 minute (voltage input to current input to output or auxiliary power)
1500 V AC @1 minute (voltage input or current input or output or auxiliary power to ground)