ES-2968 Rev.1
17PF
Rack-mounted Power Transducers 17-RACK
POWER FACTOR TRANSDUCER
Functions & Features
• Providing a DC output signal in proportion to power factor
• DC output containing little ripple is ideal for computer input
Typical Applications
• Centralized monitoring and control of power management system in a manufacturing facility or building
• Measuring power factor for a motor
MODEL: 17PF–1[1][2]6–R
ORDERING INFORMATION
• Code number: 17PF-1[1][2]6-R
Specify a code from below for each of [1] and [2].
(e.g. 17PF-11P6-R)
CONFIGURATION
1
: 3-phase / 3-wire
[1] INPUT (balanced load)
1
: 110 V / 5 A AC
2
: 110 V / 1 A AC
3
: 220 V / 1 A AC
4
: 220 V / 5 A AC
[2] OUTPUT SIGNAL POLARITY
P:
Negative in lag, positive in lead
M:
Negative in lead, positive in lag
OUTPUT
Voltage
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
AUXILIARY POWER SUPPLY
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
GENERAL SPECIFICATIONS
Construction
: Rack-mounted; terminal access via screw terminals on the front and connector on the rear; terminal cover provided
Connection
Input
: M3.5 screw terminals (torque 0.8 N·m)
Output
: Connector
Auxiliary power
: Supplied from connector
Screw terminal
: Nickel-plated steel
Isolation
: Voltage input to current input to output to auxiliary power
Computation
: Phase angle detection
Overrange output
: Approx. -10 to +120 %
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
INPUT SPECIFICATIONS
A device which employs different measuring methods may show different outputs from ours.
Frequency
: 50 or 60 Hz
• Voltage Input
Input burden
: 0.5 VA
Operational range
: 85 – 120 % of rating
Overload capacity
:
150 % of rating for 10 sec., 120 % continuous
• Current Input
Input burden
:
0.1 VA (input 1 A)
0.5 VA (input 5 A)
Operational range
: 10 – 120 % of rating
Overload capacity
: 1000 % of rating for 3 sec., 200 % for 10 sec., 120 % continuous
■
Input range
:
Lag 0.5 – 1 – lead 0.5
Lead 0.5 – 1 – lag 0.5
OUTPUT SPECIFICATIONS
INSTALLATION
Auxiliary power supply
Current consumption
: Approx. 40 mA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 40 to 85 % RH (non-condensing)
Mounting
: Standard Rack 17BXE
Weight
: 200 g (0.44 lb)
PERFORMANCE in percentage of span
Accuracy
: ±2 % with input 1 – 0.866, balanced load
±4 % with input 0.866 – 0.5, balanced load (at 23°C ±10°C or 73.4°F ±18°F, 45 – 65 Hz)
Response time
: ≤ 2 sec. (0 – 100 % ±1 %)
Ripple
: 1 %p-p max.
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 500 V AC @ 1 minute (output to auxiliary power)
2000 V AC @ 1 minute (voltage input to current input to output or auxiliary power)
1500 V AC @1 minute (voltage input or current input or output or auxiliary power to ground)
CONNECTION DIAGRAM
DIMENSIONS unit: mm (inch)
TERMINAL ASSIGNMENTS