ES-0612 Rev.9

15TS

Dual Channel Input/Output Isolators 15-RACK

THERMOCOUPLE CONVERTER

Functions & Features
• Accepting direct input from a thermocouple and providing a standard process signal
• Linearization
• Burnout protection
• High-accuracy cold junction compensation
• 2 channels available; accomplishing economical and space-saving multi-input processing
Typical Applications
• High-accuracy cold junction compensation benefits narrow span measurements
• 0.1 μA burnout sensing enables long distance transmission with minimum offset drifts
• Electric furnace (isolation)
• No burnout type can connect to a single T/C in parallel with a recorder

MODEL: 15TS–[1]6–R[2]

ORDERING INFORMATION

• Code number: 15TS-[1]6-R[2]
Specify a code from below for each of [1] and [2].
  (e.g. 15TS-26-R/BL/Q)
• Temperature range (e.g. 0 – 800°C)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] INPUT THERMOCOUPLE

1: (PR)
2: K (CA)
3: E (CRC)
4: J (IC)
5: T (CC)
6: B (RH)
  Consult us for B thermocouple
7: R
8: S
0: Specify

OUTPUT

Voltage
6: 1 – 5 V DC (Load resistance 5000 Ω min.)

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[2] OPTIONS (multiple selections)

Burnout
blank: Upscale burnout
/BL: Downscale burnout
/BN: No burnout
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Extender card (model:10EC)
 Necessary to adjust span.

GENERAL SPECIFICATIONS

Construction: Rack-mounted; terminal access via screw terminals at the front and via card-edge connector at the rear; terminal cover provided
Connection:
  Input: M3.5 screw terminals (torque 0.8 N·m)
  Output: Card-edge connector
  Power input: Suplied from card edge connector
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output or power; ch.1 input to ch.2 input
Overrange output: Approx. -10 to +120 %
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (top)
At burnout: Downscale ≤ -10 %, Upscale ≥ 110 %
Linearization: Standard
Cold junction compensation: CJC sensor attached to the input terminals (B thermocouple is without CJC as standard)

INPUT SPECIFICATIONS

Input: Thermocouples
Input resistance: 10kΩ minimum
Burnout sensing: 0.1 μA

INSTALLATION

Current consumption: Approx. 50 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 15BX
Weight: 180 g (0.40 lb)

PERFORMANCE in percentage of span

Accuracy: Refer to "Temperature range" table
Cold junction compensation error: (at 20°C ±10°C or 68°F ±18°F)
  K, E, J & T: ±0.5°C or ±0.9°F
  S, R & PR: ±1°C or ±1.8°F
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)
(at over 400°C or 750°F for R, S and PR)
Response time: ≤ 0.5 sec. (0 – 90 %)
Burnout response: ≤ 10 sec.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute (input to output or power)
500 V AC @ 1 minute (ch.1 to ch.2 input)

DIMENSIONS unit: mm (inch)