ES-0612 Rev.9
15TS
Dual Channel Input/Output Isolators 15-RACK
THERMOCOUPLE CONVERTER
Functions & Features
• Accepting direct input from a thermocouple and providing a standard process signal
• Linearization
• Burnout protection
• High-accuracy cold junction compensation
• 2 channels available; accomplishing economical and space-saving multi-input processing
Typical Applications
• High-accuracy cold junction compensation benefits narrow span measurements
• 0.1 μA burnout sensing enables long distance transmission with minimum offset drifts
• Electric furnace (isolation)
• No burnout type can connect to a single T/C in parallel with a recorder
MODEL: 15TS–[1]6–R[2]
ORDERING INFORMATION
• Code number: 15TS-[1]6-R[2]
Specify a code from below for each of [1] and [2].
(e.g. 15TS-26-R/BL/Q)
• Temperature range (e.g. 0 – 800°C)
• Specify the specification for option code /Q
(e.g. /C01)
[1] INPUT THERMOCOUPLE
1
: (PR)
2
: K (CA)
3
: E (CRC)
4
: J (IC)
5
: T (CC)
6
: B (RH)
Consult us for B thermocouple
7
: R
8
: S
0
: Specify
OUTPUT
Voltage
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS (multiple selections)
Burnout
blank
: Upscale burnout
/BL
: Downscale burnout
/BN
: No burnout
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• Extender card (model:10EC)
Necessary to adjust span.
GENERAL SPECIFICATIONS
Construction
: Rack-mounted; terminal access via screw terminals at the front and via card-edge connector at the rear; terminal cover provided
Connection
:
Input
: M3.5 screw terminals (torque 0.8 N·m)
Output
: Card-edge connector
Power input
: Suplied from card edge connector
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output or power; ch.1 input to ch.2 input
Overrange output
: Approx. -10 to +120 %
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (top)
At burnout
: Downscale ≤ -10 %, Upscale ≥ 110 %
Linearization
: Standard
Cold junction compensation
: CJC sensor attached to the input terminals (B thermocouple is without CJC as standard)
INPUT SPECIFICATIONS
Input
: Thermocouples
Input resistance
: 10kΩ minimum
Burnout sensing
: 0.1 μA
INSTALLATION
Current consumption
: Approx. 50 mA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Standard Rack 15BX
Weight
: 180 g (0.40 lb)
PERFORMANCE in percentage of span
Accuracy
: Refer to "Temperature range" table
Cold junction compensation error
: (at 20°C ±10°C or 68°F ±18°F)
K, E, J & T: ±0.5°C or ±0.9°F
S, R & PR: ±1°C or ±1.8°F
Temp. coefficient
: ±0.02 %/°C (±0.01 %/°F)
(at over 400°C or 750°F for R, S and PR)
Response time
: ≤ 0.5 sec. (0 – 90 %)
Burnout response
: ≤ 10 sec.
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 500 V AC @ 1 minute (input to output or power)
500 V AC @ 1 minute (ch.1 to ch.2 input)
DIMENSIONS unit: mm (inch)
TERMINAL ASSIGNMENTS