ES-0619 Rev.9

15SN

Dual Channel Input/Output Isolators 15-RACK

INPUT LOOP POWERED ISOLATOR

Functions & Features
• Loop-powered design eliminates output loop power supply
• 500 V DC input-to-output isolation
• 2 channels available; accomplishing economical and space-saving multi-input processing
Typical Applications
• Isolation between control room and field instrumentation, between telemetering system and input device
• Eliminates ground problems in existing systems thanks to easiness of application without requiring additional power wiring
 

MODEL: 15SN–A6[1]

ORDERING INFORMATION

• Code number: 15SN-A6[1]
Specify a code from below for [1].
  (e.g. 15SN-A6/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

INPUT

Current
A: 4 – 20 mA DC

OUTPUT

Voltage
6: 1 – 5 V DC

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS

Construction: Rack-mounted; terminal access via screw terminals at the front and via card-edge connector at the rear; terminal cover provided
Connection
  Input: M3.5 screw terminals (torque 0.8 N·m) 
  Output: Card-edge connector and M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output

INPUT & OUTPUT

Equivalent input impedance: Approx. 250 Ω with
  20 mA input
Operational range: 3 – 22 mA DC
  (Accuracy is assured within 4 – 22 mA)
Load resistance: 50kΩ minimum
•INPUT 4 – 20 mA DC / OUTPUT 1 – 5 V DC

INSTALLATION

Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 15BX
Weight: 200 g (0.44 lb)

PERFORMANCE in percentage of span

Accuracy: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(input to output)
1500 V AC @ 1 minute
(input or output to ground)
1500 V AC @1 minute (ch.1 to ch.2 input)

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]