·Some details are not shown. Please refer to specification sheets for all information.

PSN3

Final Control Elements

SERVO-TOP II ELECTRONIC ACTUATOR
(linear type; max. thrust 5000 N)

Functions & Features
• Control valve actuator drive
• Lightweight, compact design
• High reliability without electrical contacts
• Friendly user interface
• High resolution stepping motor
• Failsafe (safety shutdown) function optional

MODEL: PSN3–6[1][2]–[3][4][5]

ORDERING INFORMATION
• Code number: PSN3-6[1][2]-[3][4][5]
Specify a code from below for each of [1] through [5].
  (e.g. PSN3-631-AK3/E)
• Use Ordering Information Sheet (No. ESU-4858). Default setting (table below) will be used if not otherwise specified.

STROKE
6: 0 to 60 mm (0 to 2.36”)

[1] SEALING SPRING
1: 1500 N use
2: 3000 N use
3: 5000 N use

[2] OUTPUT STEM TYPE
1: M14 male screw, pitch 1.5
2: Stem button

[3] INPUT
Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
6: 1 – 5 V DC (Input resistance 1 MΩ min.)

[4] POWER INPUT
AC Power
K3: 100 – 120 V AC 
(Operational voltage range 90 – 132 V, 47 – 66 Hz)
 (CE not available)
L3: 200 – 240 V AC
(Operational voltage range 180 – 264 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[5] OPTIONS
Failsafe Function (emergency use)
blank: Without
/E: With

RELATED PRODUCTS
• Manual operation handle (model: HPSN)
• Programming Unit (model: PU-2x)
• Backup battery (model: PSN-BAT)

GENERAL SPECIFICATIONS
Degree of protection: IP66
Action: Direct or reverse; field selectable with DIP switches
In “reverse” action, the output stem is retracted with an input signal increase.
Operation at abnormally low input: Extend, retract or stop; field selectable with DIP switches
Detectable input drop level: 0.37 ±0.1 V DC; converted into voltage
Wiring conduits: G 1/2 female thread (two)
Terminal block: 7.62 mm pitch; M3 screw terminals (torque 0.5 N·m)
Screw terminal: Nickel-plated brass
Housing material: Aluminum alloy
Coating:  Silver color
Drive: Stepping motor
Insulation class: E
Power control element: Power MOS-FET
Position detection: Brushless angle sensor
Full-open and full-closed positions: Any point within the full stroke; minimum stroke 8 % of the full stroke; field adjustable with control buttons
Full-open/-closed (extended) signal adj.: 0 – 25 %
Full-open/-closed (retracted) signal adj.: 75 – 100 %
Extended side limiter adjustment: -5 – +25 %
Retracted side limiter adjustment: 75 – 105 %
Deadband adjustment: 0.1 – 5.0 %
Restart limiting timer adjustment: 0 – 30 sec.
Opening/closing speed adjustment: 0.22 – 4.02 mm/s
Failsafe target position adjustment: 0 – 100 % (with failsafe function only)
Isolation
  AC powered:
Signal to power to sequential signal to battery status (with failsafe function only) to metallic housing
  DC powered: Signal or power to sequential signal to battery status (with failsafe function only) to metallic housing
Fuse
  AC powered:
3 A (replaceable)
  DC powered: 4 A (replaceable)
Protective functions: Error detection, abnormal temperature increase protection, motor preheat
Power indicator: Green LED turns on with power supplied.
Input indicator: Green LED turns on with normal input
Alarm indicator: Red LED turns on in error; blinks in 1-sec. intervals when abnormal temperature increase is detected.
Manual operation: Available
Adjustments: Programming Unit (model: PU-2x); Full-open/full-closed positions, extended/retracted side limiters, full-open/full-closed signals, split range, opening/closing speed, deadband, restart limiting timer, failsafe opening/closing speed (with failsafe function only), failsafe target position (with failsafe function only)
Battery (failsafe function option)
Battery chemistry
: NiCad
Battery ambient temperature
  Charge: 0 to 55°C (32 to 131°F)
  Storage: -20 to +55°C (-4 to +131°F), short term
-20 to +45°C (-4 to +113°F), long term
  Battery life: Rechargeable up to 500 times; or 3 years, whichever is shorter, depending upon conditions of use
Drive capacity: Once
Charge method: Trickle charge after full rapid charge
Charge time: 180 minutes (completely discharged)
Battery status indicator LED: Turns on with full charge; turns off with the power removed.
Charge indicator LED: Turns on during rapid charge

INPUT SPECIFICATIONS
DC Current: Input resistor incorporated
Forced Operation: External contact signal input terminals provided for compulsory retracting or extending operation
Rating: 5 V DC @ 2.5 mA
Detection levels:
≤ 500 Ω, ≤ 1 V for ON;
≥ 10 kΩ, ≥ 4 V for OFF
Split Range: Specify split range type and split point.
Split range type: LO or HI
Split point: 30 – 70 %

OUTPUT SPECIFICATIONS
Position Signal: 4 – 20 mA DC
Load resistance: ≤ 300 Ω
Sequential Control Signal: "Full-open", "full-closed" and "alarm"
Open collector: 30 V DC @ 100 mA max.
Saturation voltage: 1 V DC
Failsafe Function (optional)
Battery status output
: Outputs a signal in synchronization with the battery status indicator; ON with full charge and OFF with the power removed.
Open collector: 30 V DC @ 100 mA
Saturation voltage: 1 V DC

INSTALLATION
Power consumption
AC: Approx. 200 VA
DC: Approx. 3 A
Operating temperature: -15 to +55°C (5 to 131°F)
Battery rechargeable within 0 to 55°C
(32 to 131°F) with failsafe function
Operating humidity: 30 to 85 %RH (non-condensing)
Vibration: ≤ 2 G (19.6 m/s2)
Mounting position: All directions
Do not mount the actuator with its output stem on the upside if the actuator is to be exposed to dripping water and rain.
Weight: 8.9 kg (18.7 lb)
10.2 kg (22.5 lb) with failsafe function

PERFORMANCE
Resolution: 0.06 mm
Insulation resistance
  AC powered
: ≥ 100 MΩ with 500 V DC
(signal to power to sequential signal to battery status (with failsafe function only) to metallic housing)
  DC powered: ≥ 100 MΩ with 500 V DC
(signal or power to sequential signal to battery status (with failsafe function only) to metallic housing)
Dielectric strength
  AC powered
: 2000 V AC @ 1 minute
(signal or metallic housing to power to battery status (with failsafe function only) to sequential signal)
500 V AC @ 1 minute (signal to metallic housing)
  DC powered: 2000 V AC @ 1 minute
(signal or power or metallic housing to battery status (with failsafe function only) to sequential signal)
500 V AC @ 1 minute (signal or power to metallic housing)

STANDARDS & APPROVALS
EU conformity (CE marking)
EMC Directive  
    EMI EN 61000-6-4
    EMS EN 61000-6-2
Low Voltage Directive 
· EN 61010-1
· Installation Category II (300V)
· Reinforced insulation:
   Power voltage to signal or seq. signals
   Power voltage to battery status (with failsafe function
   only) 
   Power voltage to metallic housing
· Pollution Degree 2
RoHS Directive
    EN IEC 63000

TERMINOLOGY
Error Detection
- When the position signal is deviated from the input signal but the output stem is stuck due to overload or certain malfunction, the PSN repeats starting the motor at the maximum torque for several items. If the stem is still stuck after that, the PSN outputs an alarm signal (LED turned ON) and stops power supply to the motor. 
- In order to reset the PSN, apply several times 0 % and 100 % input signals in turn, or turn off and on the power supply.
Abnormal Temperature Increase Protection
When the incorporated temperature sensor detects an abnormal temperature increase in the motor, the alarm LED blinks (repeating 0.5-sec. ON – 0.5-sec. OFF) and the power supply to the motor is stopped until the temperature decreases to an acceptable level. This electronic actuator is designed to resume automatically power supply to the motor. It takes longer to resume normal operation when ambient temperature is higher.
Restart Limiting Timer
This unit is equipped with a timer protecting the motor from overheating. The timer prevents the motor from restarting for a certain interval once the motor has been stopped within deadband.
When the high temperature protection is activated in a high temperature ambient, adjust the timer to a longer interval.
• Motor Preheating Function
When the internal temperature sensor detects a temperature lower than 0°C / 32°F (approximate) on the surface of the motor, the unit supplies current to the motor to warm up the motor to 0°C / 32°F.
Maintain the power supply ON when this unit is used in the ambient temperature below 0°C or 32°F.
Sealing Spring
The PSN is incorporated with springs to maintain sealing pressure when the valve is fully closed. Choose an appropriate sealing pressure.
These springs provide the same pressure at both fully closed and fully open positions.
Do not apply a greater pressure to the spring than specified.

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG Co., Ltd.