·Some details are not shown. Please refer to specification sheets for all information.

R3Y-MS8

Remote I/O R3 Series

POTENTIOMETER INPUT MODULE
(8 points, isolated, connector type)

MODEL: R3Y–MS8[1][2]

ORDERING INFORMATION
• Code number: R3Y-MS8[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R3Y-MS8W/CE/Q)
• Specify the specification for option code /Q
  (e.g. /C01/SET)

INPUT
Total resistance 500 Ω - 100 kΩ

NO. OF CHANNELS
8: 8

[1] COMMUNICATION MODE
S: Single
W: Dual

[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
 (No. ESU-8402)

RELATED PRODUCTS
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS
Connection
  Internal bus
: Via the Installation Base (model: R3-BSx)
  Input: 40-pin connector (Fujitsu FCN-365P040-AU)
  Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Input 1 to input 2 to input 3 to input 4 to input 5 to input 6 to input 7 to input 8 to internal bus or internal power
Conversion rate: Selectable with the side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with input abnormality;
Green in normal operating conditions.

INPUT SPECIFICATIONS
Minimum span: 50 % of the total resistance range
Excitation: Approx. 0.5 V DC

INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE
Conversion accuracy: Refer to the table at the end of this section.
The resolution and conversion accuracy are defined against the potentiometer's total resistance.  If the actual resistance range (between the zero and span positions) is narrower than the total resistance, the values change in proportion.  Using at least 50 % of the total resistance is basically recommended.
Conversion rate: 160 / 80 / 40 / 20 msec. selectable
Data range: 0 – 10000
Data allocation: 8
Current consumption: Approx. 100 mA
Temp. coefficient: ±0.015 % /°C
Temperature coefficient is defined against the potentiometer's total resistance. If the actual resistance range (between the zero and span positions) is narrower than the total resistance, the values change in proportion. Using at least 50 % of the total resistance is basically recommended.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute (input 1 to input 2 to input 3 to input 4 to input 5 to input 6 to input 7 to input 8 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

INPUT CONNECTOR (40-pin)

MG Co., Ltd.