·Some details are not shown. Please refer to specification sheets for all information. R3-NP1
Remote I/O R3 Series
PROFIBUS-DP INTERFACE MODULE
MODEL: R3-NP1-[1][2]
ORDERING INFORMATION
• Code number: R3-NP1-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-NP1-R/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] POWER INPUT
N: No power supply
AC Power
K3: 100 – 120 V AC
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *
(CE not available)
L3: 200 – 240 V AC
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *
(CE not available)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules or network modules with the internal power input options.
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
CAUTION
■ Mounting on 2-slot base
Use a dedicated base (R3-BS02P) for R3-NP1.
GENERAL SPECIFICATIONS
Connection
PROFIBUS: 9-pin D-sub connector, female
Internal bus: Via the Installation Base (model: R3-BSx)
Internal power: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output: M3 separable screw terminal (torque 0.5 N·m)
Screw terminal: Nickel-plated steel
Isolation: PROFIBUS to internal bus or internal power to power supply to RUN contact output to FG
Input error data setting: Input value setting at input module error with side DIP SW
Dual communication setting: Set with the side DIP switch
RUN indicator: Bi-color (green/Amber) LED
(Function selected with DIP SW)
ERR indicator: Bi-color (green/red) LED
(Function selected with DIP SW)
■
RUN CONTACT OUTPUT
RUN contact: Turns ON while the green RUN LED is ON. (PROFIBUS in normal communication)
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
Mechanical life: 2 × 10
7 cycles (300 cycles/min.)
When driving an inductive load, external contact protection and noise quenching recommended.
PROFIBUS COMMUNICATION
Interface: PROFIBUS-DP, slave (RS-485 isolation)
Max. baud rate: 12 Mbps
Protocol: DPV1
Station No. setting: Rotary switch; 00 - 7D
(Address is 7D even setting greater value)
GSD file: Msys093F.GSD
GSD files are downloadable at M-System’s web site or at PROFIBUS International site (
www.profibus.com).
Input data: Max. 240 bytes
Output data: Max. 240 bytes
Total I/O data: Max. 480 bytes
Diagnostics: Module-related, Status (devicerelated),
Channel-related (max. 32 channels, maskable)
Acyclic communication (MSAC2): 2 channels
INSTALLATION
Power consumption•
AC:
Approx. 20 VA
•
DC: Approx. 12 W
Current consumption (no power supply): 130 mA
Output current (power supply): 220 mA continuous at 20 V DC; 370 mA for 10 minutes
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (PROFIBUS to internal bus or internal power to power input to RUN output to FG)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.