·Some details are not shown. Please refer to specification sheets for all information.

R30NE1

Remote I/O R30 Series

MODBUS/TCP INTERFACE MODULE

Functions & Features
• Interchanges analog or discrete I/O signals with the filedbus (Modbus/TCP)
• Combined with R3 Series I/O modules

MODEL: R30NE1[1]

ORDERING INFORMATION
• Code number: R30NE1[1]
Specify a code from below for [1].
  (e.g. R30NE1/Q)
• Specify the specification for option code /Q
  (e.g. /C01/SET)

[1] OPTIONS
blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
 (No. ESU-9019)

CAUTION
• The internal bus communication period for R3 series I/O modules installed on the R30EBS is as follows.
Internal bus communication period = 6 msec. × number of I/O module + 10 msec. (Data update period of main CPU)
    Example: Four R3 I/O modules
        6 msec. × 4 + 10 msec. = 34 msec.
Even when the R30EBS is mounted to the R30BS, the internal bus communication period of R30 series is kept to approx. 1 msec.

RELATED PRODUCTS
• PC configurator software (model: R30CFG)
• PC configurator software (model: R3CON)
Downloadable at M-System’s web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
• R3 series I/O modules (except R3-TC2)

GENERAL SPECIFICATIONS
Connection
  Ethernet: RJ-45 connector
  Internal bus: Via the Installation Base (model: R30BS)
  Internal power: Via the Installation Base (model: R30BS)
Isolation: Ethernet to internal bus or internal power
Setting input type & input range:
 R30 series I/O module: PC configuration software (model: R30CFG)
 R3 series I/O module: PC configuration software (model: R3CON)
Internal bus communication cycle: Approx. 1 msec.
Status indicator LEDs: PWR, RUN, ERR
(Refer to the instruction manual for details.)

ETHERNET COMMUNICATION
Communication Standard: IEEE 802.3u
Transmission: 10BASE-T, 100BASE-TX
Baud rate: 10/100 Mbps (Auto Negotiation function)
Protocol: Modbus/TCP
Data: RTU (Binary)
Max. number of socket connections: 2
Transmission media: 10BASE-T (STP, Category 5), 100BASE-TX (STP, Category 5e)
Max. length of fieldbus segment: 100 meters
Ethernet indicator LEDs: LINK10, LINK100
IP address: 192.168.0.1 (factory setting);
can be set/changed using PC Configurator Software (model: R30CFG)
Port No.: 502

INSTALLATION
Current consumption: 110 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R30BS)
Weight: 105 g (0.23 lb)

PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(Ethernet to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the power supply module)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

PC CONFIGURATOR
The following parameters can be set with using PC Configurator Software (model: R30CFG)
Refer to the users manual for the R30CFG for detailed operation of the software program.

EXTERNAL VIEW

MODBUS FUNCTION CODES & SUPPORTED CODES

MODBUS I/O ASSIGNMENT

MODULE STATUS, ERROR STATUS, DATA ERROR STATUS

I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG Co., Ltd.