·Some details are not shown. Please refer to specification sheets for all information.

M6DPS2

Euro Terminal Ultra-Slim Signal Conditioners M6D Series

POWER SUPPLY MODULE
(dual redundant)

Functions & Features
• Supplies power to the M6D modules mounted on the Installation Base
• High-density mounting
• Power indicator LED
 

MODEL: M6DPS2–R[1]

ORDERING INFORMATION
• Code number: M6DPS2-R[1]
Specify a code from below for [1].
  (e.g. M6DPS2-R/UL/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 22 – 27 V, ripple 10 %p-p max.)

[1] OPTIONS (multiple selections)
Standards & Approvals
blank: CE marking
/UL: UL approval, CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating

GENERAL SPECIFICATIONS
Connection: Euro terminal (torque 0.3 N·m)
Applicable wire size: 0.2 to 2.5 mm2, stripped length 8 mm
Housing material: Flame-resistant resin (black)
Power indicator LED: Green LED turns on when the power is supplied.

INSTALLATION
Power input: 2 A (Total current consumed by signal conditioners on the base must be 2 A or less.)
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Installation Base (model: M6DBS)
Weight: 60 g (2.1 oz)

PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (power to ground)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
Approval:
  UL/C-UL nonincendive Class I, Division 2,
  Groups A, B, C, and D hazardous locations
  (ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
  UL/C-UL general safety requirements
  (UL 61010-1, CAN/CSA-C22.2 No.61010-1)

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG Co., Ltd.