·Some details are not shown. Please refer to specification sheets for all information.

M6DBS

Euro Terminal Ultra-Slim Signal Conditioners M6D Series

INSTALLATION BASE

Functions & Features
• Backplane to collectively supply power to the M6D modules in combination with the Power Supply Module (model: M6DPSx or M6-PSM)

MODEL: M6DBS–[1][2]

ORDERING INFORMATION
• Code number: M6DBS-[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. M6DBS-08/UL/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] NUMBER OF SLOTS
08: 8 slots
08P: 8 slots (for extension)
08A: 8 slots + power supply slot (for model M6-PSM)
   (UL not available)

[2] OPTIONS (multiple selections)
Standards & Approvals
blank: CE marking
/UL: UL approval, CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
Only solder side of the main PWB is coated.
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS
• M6D series signal conditioners (Not able to supply to AC power signal conditioners (M2 code))
• Power supply module (model: M6DPS1)
• Power supply module (model: M6DPS2)
• Power supply module (model: M6-PSM)
• Blank filler module (model: M6DDM)

GENERAL SPECIFICATIONS
Capacity: Up to 48 modules (including power supply module) with Extension Bases (The usable number of signal conditioners depends on the capacity of the power supply module. Refer to the M6-PSM specification sheets.)
Isolation: Power to ground

INSTALLATION
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight:
M6DBS-08, -08P: 50 g (1.8 oz) without signal conditioners
M6DBS-08A: 80 g (2.8 oz) without signal conditioners

PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (power to ground)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
Approval:
UL/C-UL nonincendive Class I, Division 2,
  Groups A, B, C, and D
  (ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
  (UL 61010-1, CAN/CSA-C22.2 No.61010-1)

EXTERNAL VIEW
Install signal conditioners from the slot at either end.
Power Supply Modules (M6DPS1 or M6DPS2) could be mounted at any slots, however,
installing them at either end is generally recommended.
Mount the power supply module (M6-PSM) on the power module slot of M6DBS-08A.

EXTERNAL DIMENSIONS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]
■ MOUNTING DIRECTION
The unit must be mounted on a vertical panel. Mounting in any other angle will cause internal temperature to rise,
may shorten the product’s life expectation or deteriorate its performance.

M-System Co., Ltd.