·Some details are not shown. Please refer to specification sheets for all information.

6BX-E

Field-mounted Two-wire Signal Conditioners 6-UNIT

OUTDOOR ENCLOSURE

Functions & Features
• Used to mount a 6-UNIT series or model B6U transmitter in outdoor environments
• Stainless steel enclosure optional

MODEL: 6BX–E–0[1]2[2][3]

ORDERING INFORMATION
• Code number: 6BX-E-0[1]2[2][3]
Specify a code from below for each of [1] through [3].
  (e.g. 6BX-E-0121/S)

SAFETY APPROVAL
0: None

[1] WIRING CONDUIT
0: G 1/2
1: 1/2 NPT
2: M20 × 1.5
3: PG 13.5

NUMBER OF CONDUITS
2: 2 places

[2] MOUNTING BRACKET
0: Without
1: With

[3] OPTIONS
Enclosure
blank: Diecast aluminium
/S: Stainless steel

PACKAGE INCLUDES...
• Mounting screws
    Bolt (M8 x 15): 4
    Spring washer for M8: 4
  Material: Stainless steel 304
• Mounting screws for the B6U Transmitter
    Screw (M4 x 30): 2
    Spring washer for M4: 2
• Mounting bracket assembly (option):
    Mounting bracket: 1
    M10 U-bolt: 2
    Nut for M10: 4
    Spring washer for M10: 4
  Material: Stainless steel 304
  Applicable pipe: 1 1/2” min.; 2” max.

GENERAL SPECIFICATIONS
Degree of protection: NEMA 4X, IP66/IP67
Wiring conduit: See ‘Ordering information.’
For use with: M-System's 6-UNIT Series, Model B6U and 43ALx, one (1) module; For detailed information and for use with other devices, consult M-System.
Material
  Enclosure: Diecast aluminium standard; SCS14 stainless steel casting optional (equivalent to type 316); silver color, epoxy resin coated

INSTALLATION
Ambient temperature: -40 to +85°C or -40 to +185°F
(Limited within the operating temperature of the device installed)
Weight
• Unit
  Approx. 1.3 kg (2.9 lb), aluminium
  Approx. 4.0 kg (8.8 lb), stainless steel
• Mounting bracket assembly (option)
  Approx. 0.78 kg (1.72 lb)

EXTERNAL DIMENSIONS unit: mm (inch)