·Some details are not shown. Please refer to specification sheets for all information.

18KJV

Rack-mounted DCS Signal Conditioners 18K-RACK

SIGNAL TRANSMITTER
(field-programmable)

Functions & Features
• Software setting of input range via programming unit (model: PU-2x) is available
• Module can be retracted without removing wiring for an insulation test

MODEL: 18KJV–[1]66–R

ORDERING INFORMATION
• Code number: 18KJV-[1]66-R
Specify a code from below for [1].
  (e.g. 18KJV-666-R)
• Special input range (For codes U1, U2 & U3)

[1] INPUT
Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
H: 10 – 50 mA DC (Input resistance 100 Ω)
Voltage
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
U1: Range ±100 mV;
(Minimum span 3 mV, Input resistance 20 kΩ min.)
U2: Range ±1000 mV;
(Minimum span 30 mV, Input resistance 20 kΩ min.)
U3: Range ±10 V;
(Minimum span 0.3 V,Input resistance 1 MΩ min.)

OUTPUT 1
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)

OUTPUT 2
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)

POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

RELATED PRODUCTS
• Programming Unit (model: PU-2x)
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw terminals on the front and connector on the rear; terminal cover provided
Connection
  Input: M3.5 screw terminals (torque 0.8 N·m)
 and connector
  Output 1: Connector
  Output 2: M3.5 screw terminals (torque 0.8 N·m)
 and connector
  Power input: Supplied from connector
Screw terminal: Nickel-plated steel
Isolation: Input to output 1 to output 2 to power
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Adjustments: Programming Unit (model: PU-2x); Input range, zero and span, simulating output, etc.
(Input range can be changed with Codes U1, U2 or U3 and limited within ranges of each code type.)
(Refer to the users manual of JXCON for the adjustments configurable with JXCON.)

INPUT SPECIFICATIONS
DC Current: Input resistor incorporated
DC Voltage: -10 – +10 V DC
Minimum span: 3 mV
Offset: Max. 3 times span
Default setting will be used if not otherwise specified.
 U1: 0 – 100 mV DC
 U2: 0 – 1 V DC
 U3: 0 – 10 V DC

OUTPUT SPECIFICATIONS
With the input voltage code 6, U3 (0 % ≥ 0 V) and current, the output goes below 0 % when the input is open.

INSTALLATION
Current consumption: Approx. 60 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 18KBXx
Weight: 150 g (0.33 lb)

PERFORMANCE in percentage of span
Accuracy: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute (input to output 1 to output 2 to power to ground)

EXTERNAL DIMENSIONS unit: mm (inch)

TERMINAL ASSIGNMENTS

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG Co., Ltd.