·Some details are not shown. Please refer to specification sheets for all information.

R30NCIE1

Remote I/O R30 Series

NETWORK MODULE
(CC-Link IE Field network)

Functions & Features
• Converts analog and discrete I/O data to the open network fieldbus (CC-Link IE Field network)
• Combined with R3 Series I/O modules

MODEL: R30NCIE1[1]

ORDERING INFORMATION
• Code number: R30NCIE1[1]
Specify a code from below for [1].
  (e.g. R30NCIE1/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS
blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS
• PC configurator software (model: R30CFG)
• PC configurator software (model: R3CON)
Downloadable at M-System’s web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
• R3 series I/O modules
The modules shown below are exceptions.
R3-PA16, R3-PA8, R3-WTU, R3-PD16, R3-DAC16, R3-RR8,
R3-GC1, R3-GD1, R3-GE1, R3-GM1, R3-GFL1

GENERAL SPECIFICATIONS
Connection
  Network: RJ-45 connector
  Internal bus: Via the Installation Base (model: R30BS)
  Internal power: Via the Installation Base (model: R30BS)
Isolation: CC-Link IE Field to internal bus or internal power
Input type & range:
 R30 series I/O module: PC configuration software (model: R30CFG)
 R3 series I/O module: PC configuration software (model: R3CON)
 Network address: PC configuration software (model: R30CFG)
Internal bus communication cycle: Approx. 1 msec.
Status indicator: RUN, RD, SD, D LINK, ERR, L ER, LINK
(Refer to the instruction manual.)

CC-Link IE Field COMMUNICATION
Protocol: IEEE 802.3
Transmission type: 1000BASE-T
Communication speed: 1 Gbps
Network cable: Cable conformed to CC-Link IE Field
Double shielded twist pair cable (CAT5e)
RJ-45 connector
Network topology: Line, star and ring
Max. number stations: 120 (Total slave station)
(Number of max. connectable slaves may vary depending on the master module. Refer to the instruction manual of the master module)
Max. station-to-station distance: 100 m
Station type: Remote device station
Link device: RX/RY 112 points, RWw/RWr 64 points
(Number of points summation of I/O module for R30 series and R3 series)

INSTALLATION
Current consumption: 160 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R30BS)
Weight: 125 g (0.28 lb)

PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (CC-Link IE Field to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the power supply module)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

EXTERNAL VIEW

TRANSMISSION DATA DESCRIPTIONS
This unit recognize type of I/O module (number of occupied station) configured the same base, and assign it to I/O Modules data with slot order automatically. However, I/O module assignment is performed only when power is turned on, in the case of changing configuration of I/O module, please turn on power again.
Keep number of station occupied of I/O module under 64, because max number of occupied station is 64 per a node. When the I/O module has space, data is transmitted close to HOST PC/PLC.
Station type: Remote device station
Link device: RX/RY 112points, RWw/RWr 64points
(Points are total of R30 series and R3series module)

E.g. I/O data is assigned as shown below in the case of following configuration.

MODULE STATUS, ERROR STATUS, DATA ERROR STATUS

I/O DATA DESCRIPTIONS
OPERATION IN CASE OF A COMMUNICATION ERROR WITH I/O MODULES
When the communication between the network module and the I/O modules is lost due to an error in an input module, the last process values are held until the communication is re-established.

EXTERNAL DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

M-System Co., Ltd.