·Some details are not shown. Please refer to specification sheets for all information.

PRP-2

Final Control Elements

SERVO-TOP II ELECTRONIC ACTUATOR
(rotary type; max. torque 600 N·m)

Functions & Features
• Control valve actuator drive
• Friendly user interface
• High resolution stepping motor
• With manual hand wheel (which does not rotate during operation)
 

MODEL: PRP-2–[1][2]–[3]

ORDERING INFORMATION
• Code number: PRP-2-[1][2]-[3]
Specify a code from below for each [1] through [3].
 (e.g. PRP-2-1A-K3)
• Use Ordering Information Sheet (No. ESU-4875). Factory setting (table below) will be used if not otherwise specified.

[1] TORQUE, OPERATION TIME
1: 600 N・m, 50 sec./90°
2: 600 N・m, 34 sec./90°
3: 600 N・m, specified time (refer to the instruction manual)

[2] INPUT
Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
6: 1 – 5 V DC  (Input resistance 20 kΩ min.)

[3] POWER SUPPLY VOLTAGE
AC Power
K3: 100 – 120 V AC
(Operational voltage range 90 – 132 V, 47 – 66 Hz)
L3: 200 – 240 V AC
(Operational voltage range 180 – 264 V, 47 – 66 Hz)

RELATED PRODUCTS (Products sold separately)
• Programming Unit (model: PU-2x)

GENERAL SPECIFICATIONS
Degree of protection: IP66
Action: Reverse or direct (In "reverse" action, the output stem turns counterclockwise (seen from the indicator) with an input signal increase.)
Field selectable with DIP switches
Operation at input failure: Stem stop at full-open, full-close or hold position at input failure; field selectable with DIP switches
Minimum input signal
  Current input: ≥ 2.0 mA DC
  Voltage input: ≥ 0.5 V DC
Wiring conduits: G 1/2 female thread (two)
Terminal block: 8.4 mm pitch; M3.5 screw terminals (torque 0.7 to 1.1 N·m)
Housing material: Aluminum alloy (type: ADC12)
Coating: Baked acrylic resin
Drive: Stepping motor
Insulation class: E
Position detection: Potentiometer (conductive plastic type)
Full-open and full-closed positions: -5 to +95°; minimum span 45°; field adjustable with control buttons
Full-closed signal adj.: -5 to +20°
Full-open signal adj.: 70 to 95°
Linearity resolution adj.: 1/300 to 1/1000
Restart limiting timer adj.: 0 to 30 sec.
Isolation: Signals to power to sequential signals to metallic housing
Fuse: 3 A (replaceable)
Manual operation: Available (manual handle stem: approx. 15 turns plus 90°/output stem: 90° action)
User-configurable items:
Configurable with Programming unit (model: PU-2x)
•Full-closed/full-open signal position
•Opening/closing speed
•Restart limiting timer
•Closed/open side limiter
•Resolution

INPUT SIGNAL SPECIFICATIONS
DC Current: Input resistor incorporated (not removable)
Forced Operation: External contact signal input terminals provided for compulsory opening or closing operation
Rating: 5 V DC @ 2.5 mA

OUTPUT SIGNAL SPECIFICATIONS
Position Signal: 4 – 20 mA DC
Load resistance: ≤ 300 Ω
Sequential Control Signal: "Full-open", "full-closed" and "alarm"
Open collector: 30 V DC @ 100 mA max.
Saturation voltage: 1 V DC

INSTALLATION
Power consumption: 180 VA
Stand-by consumption: 30 VA
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 85 %RH (non-condensing)
Vibration: Passed test condition below
•Fixed frequency endurance test
Acceleration: 2 G (19.6 m/s2)
Frequency: at resonant frequency
Endurance: 30 min.
Direction: X, Y, Z
•Sweep endurance test
Acceleration: 2 G (19.6 m/s2)
Frequency: 10 to 1000 Hz
Cycle: 20 cycles
Rate: 1 oct./min.
Endurance: approx. 4 hr. 30 min.
Direction: X, Y, Z
Mounting position: All directions
Prevent water from accumulating around the output stem.
Weight: Approx. 26.5 kg (58.42 lb)

PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC (signals to power supply voltage to sequential signals to metallic housing)
Dielectric strength:
• 2000 V AC @ 1 minute
- signals or metallic housing* to power supply voltage
- power supply voltage to sequential signals
- signals or metallic housing* to sequential signals
• 500 V AC @ 1 minute 
- signals to metallic housing
* Short between signals and metallic housing

FUNCTIONS
Error Detection
When the position signal is deviated from the input signal but the output stem is stuck due to overload or certain malfunction, the PRP repeats starting the motor at the maximum torque for several times.
If the stem is still stuck after that, the PRP outputs an alarm signal (LED turned ON) and stops power supply to the motor.
In order to reset the PRP, apply several times 0% and 100% input signals in turn, or turn off and on the power supply.
Abnormal Temperature Increase Protection
When the incorporated temperature sensor detects an abnormal temperature increase in the motor, the alarm LED blinks (repeating 0.5-sec. ON – 0.5-sec. OFF) and the power supply to the final control element motor is stopped until the temperature decreases to an acceptable level. The PRP is designed to resume automatically power supply to the motor. It takes longer to resume normal operation when ambient temperature is higher.
Restart Limiting Timer
This unit is equipped with a timer protecting the motor from overheating. The timer prevents the motor from restarting for a certain interval once the motor has been stopped within deadband.
When the high temperature protection is activated in a high temperature ambient, adjust the timer to a longer interval.
Motor Preheat Function
When this unit detects a temperature lower than 0°C or 32°F (approximate) on the surface of its motor, this unit supplies current to the motor in order to warm up and maintain its surface temperature at 5°C or 41°F (approximate).
Maintain the power-supply voltage ON when this unit is used in the ambient temperature below 0°C or 32°F.
• Resolution
The ratio that the stem of the unit rotates according to input signal.
E.g. Resolution is 1/300 for the specification that input signal is 4 to 20 mA, output stem 90°, direct or reverse action.  As the span of input signal is 16 mA (20 – 4 =
16 mA), when input signal is changed by 0.053 mA step (16 mA / 300 = 0.053 mA), the output stem rotates 0.3° (90°/ 300 = 0.3°).
(Even for output stem 60°setting, resolution is 1/300 = 0.3°step)
It is not true that input signal = output signal.
(Not input signal 4.00 mA DC = output signal 4.00 mA DC, there is difference around ±0.012 mA DC.)

EXTERNAL DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY

MG Co., Ltd.