·Some details are not shown. Please refer to specification sheets for all information.
F2AP
Super-mini Signal Conditioners F2 Series
DC/FREQUENCY CONVERTER
Functions & Features
• Providing a pulse rate output in proportion to DC input signal
• High-density mounting
Typical Applications
• Totalizing applications in combination with a counter
MODEL: F2AP–[1][2]–R[3]
ORDERING INFORMATION
• Code number: F2AP-[1][2]-R[3]
Specify a code from below for each [1] through [3].
(e.g. F2AP-61-R/Q)
• Special input range (For codes Z & 0)
• Output frequency range (e.g. 0 – 500 Hz)
• Specify the specification for option code /Q
(e.g. /C01)
[1] INPUT
Current
A
: 4 – 20 mA DC (Input resistance 250 Ω)
D
: 0 – 20 mA DC (Input resistance 50 Ω)
G
: 0 – 1 mA DC (Input resistance 1000 Ω)
H
: 10 – 50 mA DC (Input resistance 100 Ω)
Z
: Specify current (See INPUT SPECIFICATIONS)
( 0 % input must be 0 mA.)
Voltage
3
: 0 – 1 V DC (Input resistance 1 MΩ min.)
4
: 0 – 10 V DC (Input resistance 1 MΩ min.)
5
: 0 – 5 V DC (Input resistance 1 MΩ min.)
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
0
: Specify voltage (See INPUT SPECIFICATIONS)
( 0 % input must be 0 V.)
[2] OUTPUT
1
: Open collector (max. 1 kHz)
2
: 5 V pulse (max. 1 kHz)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
GENERAL SPECIFICATIONS
Construction
: Stand-alone; terminal access at the front
Connection
: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm
2
, stripped length 7 mm)
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Zero adjustment
: 0 – 5 % (front)
Span adjustment
: 95 to 105 % (front)
INPUT SPECIFICATIONS
■
DC Current
: Input resistor incorporated
Specify input resistance value for code Z.
(R ≤ 0.5 W ÷ [F.S. Current]
2
)
■
DC Voltage
: 0 – 30 V DC
Minimum span
: 1 V
Input resistance
: ≥ 1 MΩ
OUTPUT SPECIFICATIONS
■
Open Collector
: 30 V DC @100 mA (resistive load)
Frequency range
: 0 – 10 pulses/hour through 1 kHz
Saturation voltage
: 0.6 V DC
■
5 V Pulse
Frequency range
: 0 – 10 pulses/hour through 1 kHz
Hi level
: 3.0 – 5.5 V
Lo level
: ≤ 0.5 V
Load resistance
: 250 Ω min.
OUTPUT PULSE WIDTH
INSTALLATION
Current consumption
•
DC
: Approx. 80 mA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: DIN rail
Weight
: 150 g (0.33 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
Approval
:
UL/C-UL general safety requirements
(UL 3111-1, CAN/CSA-C22.2 No.1010-1)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
MG Co., Ltd.