·Some details are not shown. Please refer to specification sheets for all information.

48NAM

Bargraph Indicators 48N Series

BARGRAPH INDICATING ALARM
(potentiometer input)

Functions & Features
• Displays a process variable in graphic bargraph of 101 LED segments
• Provides max. 4 alarm contact outputs
• Multi-color indicator
• IP65 front cover
• Scale plate is easily replaced
• Separable terminal block
 

MODEL: 48NAM–[1][2][3]–[4][5]

ORDERING INFORMATION
• Code number: 48NAM-[1][2][3]-[4][5]
Specify a code from below for each [1] through [5].
(e.g. 48NAM-41V-R/CE/D/Q)
• Bargraph scale (e.g. 0 – 100 %) (See ‘Scale Plate.’)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] ALARM OUTPUT
2: 2 points
4: 4 points

[2] BAR LED COLOR
R: Red
Y: Amber
G: Green
B: Blue
1: Multi-color (red, orange and green), Pattern 1
(See ‘External View.’)
2: Multi-color (red, orange and green), Pattern 2
(See ‘External View.’)

[3] MOUNTING DIRECTION
V: Vertical
H: Horizontal

INPUT
Total resistance 100 Ω – 10 kΩ

[4] POWER INPUT
AC Power
M: 85 – 264 V AC (Operational voltage 85 – 264 V, 50/60 Hz) 
(CE marking not available)
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 50/60 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±15 %, ripple 10 %p-p max.)

[5] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
/CE: CE marking
Bezels
blank: Bezels for M-System’s 48 Series panel cutout
/D: Bezels for DIN panel cutout
/F: Bezels for Fuji Electric's PAJ, PAK, PBA panel cutout
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
Moving parts and indicators are not coated.
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

BEZEL OPTION
Bezels are used to adapt the 48N Series to an existing panel cutout. In order to replace M-System’s 48 Series products, use the one attached to the 48N Series as standard.  When the existing panel is cut according to DIN standard, specify ‘/D’ suffix code.
For a new installation, no bezel is required. Please refer to ‘Mounting Requirement’ and mount the 48N directly.
Ingress protection is invalid when the 48N is mounted with a bezel, or when multiple modules are stacked side by side.

SPARE PARTS
• Scale plate

GENERAL SPECIFICATIONS
Construction: Panel flush mounting
Degree of protection: IP65; applicable to the front panel for single unit mounted according to the specified panel cutout
Connection: M3 separable screw terminal (torque 0.6 N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Zero adjustment: 0 – 30 % of total resistance (front)
Span adjustment: 70 – 100 % of total resistance (front)
Scale plate: Flame resistant resin (white scale & characters on black base)
Setpoint adjustment
  2 points:
  H    [L setpoint ] to 100 %
  L    0 to [H setpoint]
  or No alarm trip
  4 points:
  HH    [H setpoint] to 100 %
  H    [L setpoint] to [HH setpoint]
  L    [LL setpoint] to [H setpoint]
  LL   0 to [L setpoint] 
  or No alarm trip
Alarm deadband (hysteresis): 1 %
Setting: (Front button)
• Zero and span adjustments
• Alarm setpoint
• Others
(Refer to the instruction manual for details)
BARGRAPH
LED: 101-segment LED, 100 mm (3.96”) long, 3.00 mm (.12”) wide
Display range: 0 to 100 (scaling function not available)
Scale: Two different scales available for single bargraph
Characters: Max. 4 characters including decimal point and negative sign
Divisions: Min. 22, max. 100
Engineering unit: Max. 6 characters

INPUT SPECIFICATIONS
Minimum span: 70 % of total resistance
Excitation: 0.5 V DC

OUTPUT SPECIFICATIONS
Alarm Output: Relay contact
Rated load: 250 V AC @1 A (cos ø = 1)
30 V DC @5 A (resistive load)
Maximum switching voltage: 250 V AC, 220 V DC
Maximum switching power: 380 VA, 150 W
Minimum load: 5 V DC @100 mA
Mechanical life: ≥ 5 × 108 cycles (rate 180 cycles/min.)

INSTALLATION
Power Consumption
AC:
Approx. 5.5 VA at 100 V with max. load
Approx. 7 VA at 200 V with max. load
Approx. 8 VA at 264 V with max. load
DC
Approx. 3.5 W at 20.4 V with max. load
Approx. 3.5 W at 24 V with max. load
Approx. 3.5 W at 27.6 V with max. load
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Panel flush mounting
Weight: 300 g (0.66 lb)

PERFORMANCE in percentage of span
Accuracy: ±1 % ±1 digit
Temp. coefficient: ±0.015 % of FS/°C (±0.008 % of FS/°F)
Response time: ≤ 0.5 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output to power to ground)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive
  EN 61010-1
  Measurement Category II
  Pollution Degree 2
  Input to output to power: Reinforced insulation (300 V)
RoHS Directive
  EN 50581

SCALE PLATE

EXTERNAL VIEW

DIMENSIONS unit: mm (inch)

PANEL CUTOUT unit: mm

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG Co., Ltd.