·Some details are not shown. Please refer to specification sheets for all information.
15YK
Dual Channel Input/Output Isolators 15-RACK
OUTPUT ISOLATOR
(fast response)
Functions & Features
• Converting a DC input into an isolated standard process signal
• Input from the Standard Rack connector can be monitored at the front terminals
• 2 channels available; accomplishing economical and space-saving multi-output processing
Typical Applications
• Isolation between control room and field instrumentation
MODEL: 15YK–6[1]–R[2]
ORDERING INFORMATION
• Code number: 15YK-6[1]-R[2]
Specify a code from below for each [1] and [2].
(e.g. 15YK-66-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
INPUT
Voltage
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
[1] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
6
: 1 – 5 V DC (Load resistance 500 Ω min.)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• EXTENDER CARD (model:10EC)
Necessary to adjust span.
GENERAL SPECIFICATIONS
Construction
: Rack-mounted; terminal access via screw terminals at the front and via card-edge connector at the rear; terminal cover provided
Connection
Input
: Card-edge connector
Output, input monitor
: M3.5 screw terminals (torque 0.8 N·m)
Power input
: Supplied from card-edge connector
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input or output to power; ch.1 output to ch.2 output
Overrange output
: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (top)
OUTPUT SPECIFICATIONS
With the input voltage code 3, 4, 5, 6 and current, the output goes below 0 % when the input is open.
INSTALLATION
Power consumption
: Approx. 30 mA with voltage output; approx. 70 mA with current output
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Standard Rack 15BX
Weight
: 200 g (0.44 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 25 msec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 500 V AC @ 1 minute
(input or power to output)
500 V AC @ 1 minute (ch.1 to ch.2 output)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
MG Co., Ltd.