R3-WTU
Remote I/O R3 Series
MULTI POWER INPUT MODULE
(clamp-on current sensor type CLSE use)
Functions & Features
• Measures simultaneously several variables of a heavy-current power system including computing bidirectional current, phase and harmonics
• 1 or 2 systems
• Uses clamp-on current sensors; No need of current transformers
• Current sensors are easy to install in existing systems
Typical Applications
• Energy demand management in manufacturing
plants and buildings
• Multi-functional power monitor incorporated in electric devices or in switching boards: saves space, wiring works, and cost
MODEL: R3–WTU1[1]ES[2]
ORDERING INFORMATION
• Code number: R3-WTU1[1]ES[2]
Specify a code from below for each [1] and [2].
(e.g. R3-WTU12ES/D/Q)
• Specify the specification for option code /Q
(e.g. /C01)
CONFIGURATION
1
: Single-phase / 2-wire and 3-wire,
3-phase / 3-wire and 4-wire
[1] NO. OF SYSTEMS
1
: 1 system
2
: 2 systems
INPUT
E
: 480 V AC / Sensor type CLSE
COMMUNICATION MODE
S
: Single
[2] OPTIONS (multiple selections)
Data Capacity (address/slot occupied)
blank
: 16 words (1)
/D
: 32 words (2)
Be sure to use the R3-BSW base with free address setting
capability. Refer to ‘TRANSMISSION DATA DESCRIPTIONS.’
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• PC configurator software (model: R3CON)
Downloadable at M-System’s web site.
• Clamp-on current sensor (model: CLSE)
The clamp-on current sensors, not included in this product package, must be ordered separately. Required number depends upon the system configuration.
• Network module (model: R3-Nx)
In order to have the reset function from the host device, use V.2.00 or higher versions of the R3-NC1, -NC3, -NE1 and -NM1. With other versions and models, the resetting is possible using the R3CON PC Configurator.
For use with the R3-NLx, consult M-System.
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R3-BSx)
Voltage input
: Separable terminal block
(applicable wire dia. ≤ 2.5, 0.5 – 3.5 mm
2
, stripped
length 7 mm)
Current input
: Separable terminal block
(applicable wire dia. ≤ 2.4, 0.5 – 3.5 mm
2
, stripped
length 10 mm)
Internal
Power
: Via the Installation Base (model: R3-BSx)
Configuration
: Single phase/2-wire and 3-wire, 3-phase/3-wire balanced/unbalanced load, 3-phase/4-wire balanced/unbalanced load
Isolation
: Sensor core to sensor output or current input or voltage input to internal bus or internal power
Measured variables
Voltage
: 1 – N, 2 – N, 3 – N, 1 – 2, 2 – 3, 3 – 1
Current
: 1, 2, 3, N
Active / reactive / apparent power
: 1, 2, 3, Σ
Power factor
: 1, 2, 3, Σ
Frequency
Active energy
: Incoming / outgoing
Reactive energy
: Incoming / outgoing / lag (inductive)
/lead (capacitive)
Apparent energy
Active / reactive / apparent power intervals (demand)
Average (demand) current
: 1, 2, 3, N
Harmonic contents
: Σ
Voltage: 1 – N, 2 – N, 3 – N, 1 – 2, 2 – 3, 3 – 1
Current: 1, 2, 3, N
Max. and min. values
Demand history
: 1 to 4
(Programmable within 1 – 60 min.; factory set to 30 min.)
RUN indicator
: Bi-color (red/green) LED;
Red when the internal bus operates normally.
ERR indicator
: Bi-color (red/green) LED;
Red with the input abnormality (input ≥ 120 %, frequency out of 45 – 65 Hz range);
Green in normal operating conditions.
Low-end cutout
: Converted as 0 % for the input below a preset value; programmable within 0 – 99.9 %; factory set to 1 %
Data resetting
: All energy values, MAX / MIN current values, MAX / MIN values other than current, AVG (demand) values
(The resetting from the host is possible by using V.2.00 or higher versions of the R3-NC1, -NC3, -NE1 and -NM1.)
INPUT SPECIFICATIONS
Frequency
: 50 / 60 Hz (45 – 65 Hz)
•
Voltage Input
Rated voltage
Line-to-line (delta voltage): 480 V
Line-neutral (phase voltage): 277 V (single-phase / 2-wire and 3-wire)
Consumption VA
: ≤ U
LN
2
/ 300 kΩ / phase
Overload capacity
: 200 % of rating for 10 sec., 120 % continuous
Selectable primary voltage range
: 50 – 400 000 V
•
Current Input
CLSE-R5
: 0 – 5 A AC
CLSE-05
: 0 – 50 A AC
CLSE-10
: 0 – 100 A AC
CLSE-20
: 0 – 200 A AC
CLSE-40
: 0 – 400 A AC
CLSE-60
: 0 – 600 A AC
Overload capacity
: 120 % continous, 500 % for 10 sec.
(Note: Use for the circuit not exceed 480 V)
Selectable primary current range
: 1 – 20 000 A (only with CLSE-R5, refer to the configurator settings)
Operational range
Current
: 0 – 115 % of the rating
Voltage, apparent power
: ≤ 120 % of the rating
Active/reactive power
: ±120 % of the rating
Frequency
: 45 – 65 Hz
Power factor
: ±1
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Use the R3-BSW with Option /D.
Weight
: 170 g (0.37 lb)
PERFORMANCE in percentage of span
Accuracy
(at 23°C ±10°C or 73.4°F ±18°F, 45 – 65 Hz)
Add the accuracy of the current sensor for overall values.
Voltage
: ±1.0 % of the rating
Current
: ±1.0 % of the rating
Power
: ±1.0 % of the rating
Power factor
: ±3.0 %
Frequency
: ±1.0 % of the rating
Energy
: ±2 %
Harmonic contents
: ±2.5 % of the rating
Conversion data
: 16 bits / 32 bits
Data allocation mode
: 16 or 32
(Refer to ‘TRANSMISSION DATA DESCRIPTIONS.’)
Current consumption
: 60 mA
Input response time
: ≤ 2 sec. (0 – 100 % ±1 %)
≤3 sec. for frequency and harmonic contents
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (voltage input or current input to internal bus or internal power)
2000 V AC @ 1 minute (sensor core to sensor output)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
TRANSMISSION DATA DESCRIPTIONS
■
MEASURANDS
• 16-word Mode (standard)
Measurands and assigned word numbers are specified using the R3CON PC Configurator.
Max. 16 words per module (slot). 1 word = 16 bits, 2 words
= 32 bits
• 32-word Mode (option /D)
Measurands and assigned word numbers are specified using the R3CON PC Configurator.
Max. 32 words by virtually assigning addresses (n) and (n+1) per module. 1 word = 16 bits, 2 words = 32 bits
Be sure to use the R3-BSW base with free address setting capability. DO NOT assign the address (n+1) to any module.
A duplicate address will cause malfunctions.
■
RESET
Measurands to be reset can be specified among: all energy values, MAX / MIN current values, MAX / MIN values other than current and AVG (demand) values.
Refer to ‘I/O DATA DESCRIPTIONS’ in the R3-WTU instruction manual for resetting from the host device.
For detailed information for the selection of measurands and other settings, refer to the R3CON Users Manual.
EXTERNAL VIEW
DIMENSIONS unit: mm (inch)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM