·Some details are not shown. Please refer to specification sheets for all information.

R5T-DC4

Remote I/O R5 Series

DISCRETE OUTPUT MODULE
(screw terminal block; relay contact output, 4 points)

MODEL: R5T–DC4[1][2]

ORDERING INFORMATION
 Code number: R5T-DC4[1][2]
Specify a code from below for each [1] and [2].
 (e.g. R5T-DC4W/Q)
• Specify the specification for option code /Q
 (e.g. /C01/S01)

NO. OF CHANNELS
4: 4-point outputs

[1] COMMUNICATION MODE
S: Single
W: Dual

[2] OPTIONS
blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

GENERAL SPECIFICATIONS
Connection
  Internal bus: Via the Installation Base
  (model: R5-BS)
  Output: M3.5 screw terminal block (torque 0.8 N·m)
  Internal power: Via the base (model: R5-BS)
Screw terminal: Nickel-plated steel (standard) or stainless steel
Isolation: Do1 or Do2 to Do3 or Do4  to internal bus or internal power
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
Output status indicator: Red LED; turns on with the outputs ON.

OUTPUT SPECIFICATIONS
Output: Relay contact, 4 points
Common: Every 2 points
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
Mechanical life: 2 × 107 cycles (rate 300/min.)
When driving an inductive load, external contact protection and noise quenching recommended.

INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R5-BS)
Weight: 110 g (0.24 lb)

PERFORMANCE
Data allocation: 1
Response time: ≤ 0.1 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (Do 1 or Do 2 to Do 3 or Do 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive 
  EN 61010-1, EN 61010-2-201
  Installation Category II
  Pollution Degree 2
  Contact output to internal bus or internal power – Basic insulation
  (300 V)
RoHS Directive
  EN 50581

FUNCTIONS
Output hold function:
In normal conditions, the module outputs the signal from the preferred bus A.
When an error is detected, the output is switched to the data from the bus B.
If both are in error, the module holds the signal and stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is established and normal data is received.

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG Co., Ltd.