·Some details are not shown. Please refer to specification sheets for all information.

M2BS-16

Super-mini Signal Conditioners Mini-M Series

INSTALLATION BASE (16 positions)

Functions & Features
• Receiving at the maximum of 16 modules of Mini-M series signal conditioners
• Screw terminal or connector output
• Power supplied through printed wiring on the base

MODEL: M2BS–16[1][2]

ORDERING INFORMATION
• Code number: M2BS-16[1][2]
Specify a code from below for each [1] and [2].
(e.g. M2BS-16U2/D/UL)

[1] FUNCTION
U0: Screw terminal block
U1: Fujitsu FCN type I/O connector  (UL not available)
U2: Omron I/O connector

[2] OPTIONS (multiple selections)
Mounting
blank: Surface
/D: DIN rail mounting adaptor (Not selectable for M2BS-16U0)
Standards & Approvals
blank: Without UL
/UL: UL approval

RELATED PRODUCTS
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS
Capacity: 16 positions
Connection
  Power input
: M3 screw terminals (torque 0.8 N·m)
  Input and output: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel

INSTALLATION
Power input: Refer to signal conditioner data sheet.  Choose the same power input specification for all units.
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface; optional DIN rail mounting available
for M2BS-16U1, U2 (in horizontal direction only)
Weight: 1.8 kg (4.0 lb)

PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
(input to output to power to FG)
Dielectric strength: 2000 V AC @1 minute  (input to output to power to FG)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive
  EN 61010-1
  Installation Category II
  Pollution Degree 2
  Input or output to power: Reinforced insulation (300 V)
  Input to output: Basic insulation (300 V)
RoHS Directive
  EN 50581
Approval:
UL/C-UL nonincendive Class I, Division 2,
  Groups A, B, C, and D
  (ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
  (UL 3111-1, CAN/CSA-C22.2 No.1010-1)
Voltage at the field I/O terminals (except power input terminals) limited within 30 V DC for UL.

CONNECTION DIAGRAM

DIMENSIONS unit: mm (inch)

MOUNTING REQUIREMENTS unit: mm (inch)

MG Co., Ltd.