MD6T-65

Lightning Surge Protectors for
Electronics Equipment M-RESTER

LIGHTNING SURGE PROTECTOR FOR
STANDARD SIGNAL LINE & PULSE USE
(conduit mount, weather-proof; 65 V DC line voltage)

Functions & Features
• Designed specifically for 4 – 20 mA DC and pulse signal line including both 4-wire and 2-wire transmitters
• Direct mount in a wiring conduit of outdoor
enclosures
• Absorbs surges only without affecting instrumentation signal

MODEL: MD6T–65–[1][2][3]

ORDERING INFORMATION
• Code number: MD6T–65–[1][2][3]
Specify a code from below for each [1] through [3].
(e.g. MD6T-65-00B)
For the safety approval code 4, specify the product’s destination country using Ordering Information Sheet (No. ESU-8284).

[1] SAFETY APPROVAL
0: None
4: CENELEC flameproof (ATEX)

[2] WIRING CONDUIT
0: G 1/2 (Not selectable for CENELEC flameproof approval)
1: 1/2 NPT
2: M20 × 1.5

[3] BODY MATERIAL
B: Brass
S: Stainless steel

CAUTION
The packing of the cable gland must be separate from the body. Choose an appropriate one for the environment in which the surge protector is used.

GENERAL SPECIFICATIONS
Degree of protection: IP65
Wiring conduit: See ‘Ordering information.’
Connection
  Cable side
: Terminal block (leadwire diameter: 0.14 – 1.5 mm2 for both stranded and solid wires; or AWG26 – 16)
  Equipment side: Leadwires (leadwire diameter AWG20 for grounding; AWG22 for the protected equipment)
Body material: Nickel-plated brass or stainless steel 316

INSTALLATION
Operating temperature: -40 to +85°C (-40 to +185°F)
(See Safety Parameters for use in a hazardous
location.)

Mounting: Screwed into an electrical conduit of outdoor enclosures
Weight: 500 g (1.1 lb)

PERFORMANCE
Discharge voltage (peack voltage)
  Line to line: 70 V min.
  Line to ground: ±160 V min.
Max. surge voltage
  Line to line: 100 V max. 
  Line to ground: ±650 V max.
(The maximum voltage that could pass through the surge protector. Protected equipment must be able to withstand this voltage for a very short time period.)
Response time:
 Line to line: ≤ 4 nsec.
 Line to ground: ≤ 20 nsec.
Leakage current:
  Line to line: ≤ 5 μA @ 70 V DC
  Line to ground: ≤ 5 μA @ ±160 V DC
Discharge current capacity: 10000 A (8/ 20 μsec.)
Max. load current: 100 mA
Internal series resistance: Approx. 22 Ω including return
Max. line voltage 
  Without safety approval: 70 V DC
  With safety approval: 66 V DC
Capacitance @ 1 kHz:
 Line to line:  ≤ 2500 pF
 Line to ground: ≤ 100 pF

STANDARDS & APPROVALS
EU conformity:
ATEX Directive 
  Ex d EN 60079-1
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581
Safety approval:

SAFETY PARAMETERS
Operating temperature:
  T5 -40 to +80°C
  T6 -40 to +75°C
    -40 to +75°C for CENELEC (ATEX) flameproof

CONNECTION EXAMPLES

DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

M-System Co., Ltd.