·Some details are not shown. Please refer to specification sheets for all information.

R3-DC64C

Remote I/O R3 Series

DISCRETE OUTPUT MODULE
(PNP transistor output, 64 points, shortcircuit protection)

MODEL: R3–DC64C[1][2]

ORDERING INFORMATION
• Code number: R3-DC64C[1][2]
Specify a code from below for each [1] and [2].
 (e.g. R3-DC64CW/CE/Q)
• Specify the specification for option code /Q
 (e.g. /C01)

NO. OF CHANNELS
64: 64

OUTPUT
C: PNP transistor

[1] COMMUNICATION MODE
S: Single
W: Dual

[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS
Connection
  Internal bus
: Via the Installation Base (model: R3-BSx)
  Output: 40-pin connector (Fujitsu FCN-365P040-AU)
  Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Do11 thru Do18 to Do21 thru Do28 to Do31 thru Do38 to Do41 thru Do48 to Do51 thru Do58 to Do61 thru Do68 to Do71 thru Do78 to Do81 thru Do88 to internal bus or internal power
Output hold function: Setting for communication error with side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Green in normal operating conditions.
Output status indicator: Red LED; turns on with the output ON.
Group selector: Switches the status LED channels
CN1:
 A. 1 - 8: Do11 - Do18, 9 - 16: Do21 - Do28
 B. 1 - 8: Do31 - Do38, 9 - 16: Do41 - Do48
CN2:
 A. 1 - 8: Do51 - Do58, 9 - 16: Do61 - Do68
 B. 1 - 8: Do71 - Do78, 9 - 16: Do81 - Do88

OUTPUT SPECIFICATIONS
Output: Open collector, 64 points
Isolation: Optical isolator
Rated load voltage
 Nominal: 19.2 to 30 V DC
 Absolute: 45 V DC
Rated load current: 0.25 A per point, 1.0 A per common
Voltage drop at ON: ≤ 2.0 V
Leakage current at OFF: ≤ 0.3 mA
(24 V DC load, all points OFF)
ON delay: ≤ 1.0 msec.
OFF delay: ≤ 3.5 msec.
Shortcircuit protection: Works for 0.7 A or more; automatically resets after recovery

INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE
Data allocation: 4
Current consumption: 160 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(Do11 thru Do18 to Do21 thru Do28 to Do31 thru Do38 to Do41 thru Do48 to Do51 thru Do58 to Do61 thru Do68 to Do71 thru Do78 to Do81 thru Do88)
1500 V AC @ 1 minute (output to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

FUNCTIONS
OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from the preferred bus A.
When an error is detected, the output is switched to the data from the bus B.
Output Hold
If both are in error, the module holds the signal and stands by until one of the communications recovers.
Output OFF
If both are in error, the module outputs OFF signals and stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is established and normal data is received.

EXTERNAL VIEW

DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

OUTPUT CONNECTOR (40-pin)

MG Co., Ltd.