ES-3319 Rev.8

TSN

Super-mini Two-wire Signal Conditioners T-UNIT

INPUT LOOP POWERED ISOLATOR

Functions & Features
• Loop-powered design eliminates output loop power supply
• 500 V DC input-to-output isolation
• Highdensity mounting
Typical Applications
• Isolation between control room and field instrumentation, between telemetering system and input device
• Eliminates ground problems in existing systems thanks to easiness of application without requiring additional power wiring
 

MODEL: TSN–[1]

ORDERING INFORMATION

• Code number: TSN-[1]
Specify a code from below for [1].
  (e.g. TSN-H6)

[1] INPUT / OUTPUT

blank: 4 – 20 mA DC / 1 – 5 V DC
H6: 10 – 50 mA DC / 1 – 5 V DC

GENERAL SPECIFICATIONS

Construction: Stand-alone; terminal access at the front
Connection: Euro type terminal
(applicable wire size: 0.25 to 1.5 mm2, stripped length 
7 mm)
Housing material: Flame-resistant resin (black)
Isolation: Input to output
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)

INPUT & OUTPUT

■ Input 4 – 20 mA DC / OUTPUT 1 – 5 V DC
Equivalent input impedance
: Approx. 250 Ω with 20 mA input
Operational range: 3 – 22 mA DC
(Accuracy is assured within 4 – 22 mA)
Load resistance: 50 kΩ min.
■ Input 10 – 50 mA DC / OUTPUT 1 – 5 V DC
Equivalent input impedance
: Approx. 100 Ω with 50 mA input
Operational range: 7 – 55 mA DC
(Accuracy is assured within 8 – 55 mA)
Load resistance: 50 kΩ minimum
•INPUT 4 – 20 mA DC / OUTPUT 1 – 5 V DC
•INPUT 10 – 50 mA DC / OUTPUT 1 – 5 V DC

INSTALLATION

Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 120 g (0.26 lb)

PERFORMANCE in percentage of span

Accuracy: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute (input to output)

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]